Triplex Service Drop Aluminum Conductor
triplex-service-drop-br-aluminum-conductor
-
Triplex Service Drop Aluminum Conductors - AAC Neutral Messenger
Applications
To supply power from the utility's lines to the consumer's weatherhead. For service at 600 volts or less (phase to phase) at a conductor temperature of 75 ºC maximum for polyethylene Insulation or 90 ºC maximum for crosslinked insulation.
Construction
Concentric strand or compressed 1350-H19 conductor, polyethylene or crosslinked polyethylene insulation, concentric strand AAC neutral messenger.
Standards- B-230 Aluminum Wire 1350-H19 for Electrical Purposes.
- B-231 Aluminum Conductors, Concentric-Lay-Stranded.
- B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR).
- B-399 Concentric-Lay-Stranded 6201-T81 Aluminum Alloy Conductors.
- B-498 Zinc-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR).
- Triplex Service Drop cable meets or exceeds all applicable requirements of ANSI/ICEA body S-76-474.
-
Triplex Service Drop Aluminum Conductors - ACSR Full Size Messenger
Applications
To supply power from the utility's lines to the consumer's weatherhead. For service at 600 volts or less (phase to phase) at a conductor temperature of 75 ºC maximum for polyethylene Insulation or 90 ºC maximum for crosslinked insulation.
Construction
Concentric strand or compressed 1350-H19 conductor, polyethylene or crosslinked polyethylene insulation, concentric strand ACSR neutral messenger.
Standards- B-230 Aluminum Wire 1350-H19 for Electrical Purposes.
- B-231 Aluminum Conductors, Concentric-Lay-Stranded
- B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR).
- B-309 Concentric-Lay-Stranded 6201-T81 Aluminum Alloy Conductors.
- B-498 Zinc-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR).
- Triplex Service Drop cable meets or exceeds all applicable requirements of ANSI/ICEA body S-76-474.
-
Triplex Service Drop Aluminum Conductors - ACSR Reduced Size Messenger
Applications
To supply power from the utility's lines to the consumer's weatherhead. For service at 600 volts or less (phase to phase) at a conductor temperature of 75 ºC maximum for polyethylene Insulation or 90 ºC maximum for crosslinked insulation.
Construction
Concentric strand or compressed 1350-H19 conductor, polyethylene or crosslinked polyethylene insulation, concentric strand ACSR neutral messenger.
Standards- B-230 Aluminum Wire 1350-H19 for Electrical Purposes.
- B-231 Aluminum Conductors, Concentric-Lay-Stranded
- B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR).
- B-309 Concentric-Lay-Stranded 6201-T81 Aluminum Alloy Conductors.
- B-498 Zinc-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR).
- Triplex Service Drop cable meets or exceeds all applicable requirements of ANSI/ICEA body S-76-474.
-
Triplex Service Drop Aluminum Conductor - AAAC 6201 Alloy Full Size Neutral Messenger
Applications
To supply power from the utility's lines to the consumer's weatherhead. For service at 600 volts or less (phase to phase) at a conductor temperature of 75 ºC maximum for polyethylene Insulation or 90 ºC maximum for crosslinked insulation.
Construction
Concentric strand or compressed 1350-H19 conductor, polyethylene or crosslinked polyethylene insulation, concentric strand 6201 alloy neutral messenger.
Standards- B-230 Aluminum Wire 1350-H19 for Electrical Purposes.
- B-231 Aluminum Conductors, Concentric-Lay-Stranded.
- B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR).
- B-399 Concentric-Lay-Stranded 6201-T81 Aluminum Alloy Conductors.
- B-498 Zinc-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR).
- Triplex Service Drop cable meets or exceeds all applicable requirements of ANSI/ICEA body S-76-474
-
Triplex Service Drop Aluminum Conductor - AAAC 6201 Alloy Reduced Size Neutral Messenger
Applications
To supply power from the utility's lines to the consumer's weatherhead. For service at 600 volts or less (phase to phase) at a conductor temperature of 75 ºC maximum for polyethylene Insulation or 90 ºC maximum for crosslinked insulation.
Construction
Concentric strand or compressed 1350-H19 conductor, polyethylene or crosslinked polyethylene insulation, concentric strand 6201 alloy neutral messenger.
Standards- B-230 Aluminum Wire 1350-H19 for Electrical Purposes.
- B-231 Aluminum Conductors, Concentric-Lay-Stranded.
- B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR).
- B-399 Concentric-Lay-Stranded 6201-T81 Aluminum Alloy Conductors.
- B-498 Zinc-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR).
- Triplex Service Drop cable meets or exceeds all applicable requirements of ANSI/ICEA body S-76-474
-
PACKAGING INFORMATION: Triplex Service Drop Aluminum Conductor
Packaging Information: Triplex Service Drop Aluminum Conductor CODE WORD ALUMINUM
CONDUCTORSSTANDARD PACKAGE SIZES PHASE
SIZE AND STRANDINGNEUTRAL SIZE AND STRANDING LENGTH WEIGHT PE
(lbs)WEIGHT XLP
(lbs)REEL
SIZEAAC Neutral Messenger Patella 6-7 6-7 1000 104 107 Coil 2,200 229 235 NRC 30.18 Oyster 4-7 4-7 500 77 79 Coil 1500 230 237 NRC 30.18 Clam 4-7 4-7 500 116 119 Coil 1800 418 428 NRC 36.24 Murex 1/0-7 1/0-7 500 187 192 Coil 1200 448 460 NRC 36.24 Purpura 1/0-19 1/0-7 500 185 190 Coil 1200 444 456 NRC 36.24 Nassa 2/0-7 2/0-7 1500 692 708 NRC 42.26 Trophon 2/0-19 2/0-7 1500 684 701 NRC 42.26 Quahog 3/0-7 3/0-7 1300 741 758 NRC 42.26 Melita 3/0-19 3/0-19 1300 735 750 NRC 42.26 Coquina 4/0-7 4/0-7 1000 707 722 NRC 42.26 Portunus 4/0-19 4/0-19 1000 699 713 NRC 42.26 ACSR Messenger Voluta 6-7 6-6/1 1,000 115 118 Coil 2,200 253 260 NRC 30.18 Periwinkle 4-7 4-6/1 500 86 88 Coil 1,500 238 264 NRC 30.18 Conch 4-7 2-6/1 500 131 134 Coil 1,800 470 481 NRC 36.24 Neritina 1/0-7 1/0-6/1 500 210 215 Coil 1,200 503 516 NRC 36.24 Cenia 1/0-19 1/0-6/1 500 208 213 Coil 1,200 499 511 NRC 36.24 Runcina 2/0-7 2/0-6/1 1,500 779 795 NRC 42.26 Triton 2/0-19 2/0-6/1 1,500 771 789 NRC 42.26 Cherrystone 3/0-7 3/0-6/1 1,300 836 853 NRC 42.26 Mursia 3/0-19 3/0-6/1 1,300 829 845 NRC 42.26 Razor 4/0-7 4/0-6/1 1,000 799 814 NRC 42.26 Zuzara 4/0-19 4/0-6/1 1,000 792 806 NRC 42.26 Limpet 336.4-19 336.4-18/1 1,000 1150 1180 NRC 42.26 ACSR Reduced Size Messenger Strombus 4-7 6-6/1 500 76 78 Coil 1,500 228 233 NRC 30.18 Cockle 2-7 4-6/1 500 114 117 Coil 1,800 409 419 NRC 36.24 Janthina 1/0-7 2-6/1 500 183 188 Coil 1,200 438 451 NRC 36.24 Ranella 1/0-19 2-6/1 500 181 186 Coil 1,200 434 446 NRC 36.24 Cavolinia 2/0-7 1-6/1 1,500 677 693 NRC 42.26 Clio 2/0-19 1-6/1 1,500 669 687 NRC 42.26 Sanddollar 3/0-7 10-6/1 1,300 724 741 NRC 42.26 Aega 3/0-19 10-6/1 1,300 718 735 NRC 42.26 Cuttlefish 4/0-7 2/0-6/1 1,000 691 706 NRC 42.26 Cerapus 4/0-19 2/0-6/1 1,000 684 699 NRC 42.26 Aluminum Alloy 6201-T81 Messenger Hippa 6-7 6-7 500 54 56 Coil 2,000 214 222 NRC 30.18 Prawn 4-1 4-7 500 77 79 Coil 1,700 260 269 NRC 30.18 Barnacles 4-7 4-7 500 80 83 Coil 1500 240 248 NRC 30.18 Shrimp 2-7 2-7 500 121 125 Coil 1800 436 448 NRC 36.24 Gammarus 1/0-7 1/0-7 500 195 200 Coil 1200 468 480 NRC 36.24 Leda 1/0-19 1/0-7 500 193 198 Coil 1200 463 475 NRC 36.24 Dungenese 2/0-7 2/0-7 1500 723 740 NRC 42.26 Cyclops 2/0-19 2/0-7 1500 716 732 NRC 42.26 Stonecrab 3/0-7 3/0-7 1300 775 792 NRC 42.26 Flustra 3/0-19 3/0-7 1300 768 784 NRC 42.26 Kingcrab 4/0-7 4/0-7 1000 740 755 NRC 42.26 Lepas 4/0-19 4/0-7 1000 733 746 NRC 42.26 Aluminum Alloy 6201-T81 Reduced Size Messenger Crab 4-7 6-7 500 72 74 Coil 1,500 215 222 NRC 30.18 Solaster 2-7 4-7 500 108 111 Coil 1,800 367 400 NRC 36.24 Sandcrab 1/0-7 2-7 500 174 179 Coil 1,200 416 428 NRC 36.24 Echinus 1/0-19 2-7 500 172 177 Coil 1,200 412 424 NRC 36.24 Crayfish 2/0-7 1-7 1,500 641 659 NRC 42.26 Sipho 2/0-19 1-7 1,500 635 651 NRC 42.26 Slub 3/0-7 1/0-7 1,300 686 703 NRC 42.26 Fulgar 3/0-19 1/0-7 1,300 680 696 NRC 42.26 Squid 4/0-7 2/0-7 1,000 654 669 NRC 42.26 Arca 4/0-19 2/0-7 1,000 647 661 NRC 42.26