USE-2 / RHH / RHW-2 Direct Burial Aluminum Conductor 600V, 90°C Wet or Dry
Aluminum XLP UL RHH/RHW-2 or USE-2 90ºC 600V
Applications
Type USE-RHH-RHW-2 building wire and service cable is recognized for use as general purpose wiring at a maximum conductor temperature of 90ºC in wet or dry locations for installation in air, conduit or other recognized raceways and for direct burial in circuits not exceeding 600 volts.
Construction
Compact stranded 8000 Series aluminum alloy conductor, black abrasion, heat, moisture and sunlight resistant cross-linked polyethylene insulation.
Standards
To determine correct ampacity by conductor size, please consult the National Electric Code, the latest edition.
Type USE-RHH-RHW-2 building wire and service cable is recognized for use as general purpose wiring at a maximum conductor temperature of 90ºC in wet or dry locations for installation in air, conduit or other recognized raceways and for direct burial in circuits not exceeding 600 volts.
Construction
Compact stranded 8000 Series aluminum alloy conductor, black abrasion, heat, moisture and sunlight resistant cross-linked polyethylene insulation.
Standards
- UL Standards 44 (RHW or RHH)
- UL standard 854 (USE-2)
- Federal specification JC-30B NEC
- ASTM B800, B801, B836 as applicable.
To determine correct ampacity by conductor size, please consult the National Electric Code, the latest edition.
Unit of Measure
Items |
/Asset/AL-USE-2-RHH-RHW-2.jpg USE-RHH-RHW-2-0008 USE-2 / RHH / RHW-2 Direct Burial Aluminum Conductor 600V, 90°C Wet or Dry |
/Asset/AL-USE-2-RHH-RHW-2.jpg USE-RHH-RHW-2-0006 USE-2 / RHH / RHW-2 Direct Burial Aluminum Conductor 600V, 90°C Wet or Dry |
/Asset/AL-USE-2-RHH-RHW-2.jpg USE-RHH-RHW-2-0004 USE-2 / RHH / RHW-2 Direct Burial Aluminum Conductor 600V, 90°C Wet or Dry |
/Asset/AL-USE-2-RHH-RHW-2.jpg USE-RHH-RHW-2-0002 USE-2 / RHH / RHW-2 Direct Burial Aluminum Conductor 600V, 90°C Wet or Dry |
/Asset/AL-USE-2-RHH-RHW-2.jpg USE-RHH-RHW-2-0001 USE-2 / RHH / RHW-2 Direct Burial Aluminum Conductor 600V, 90°C Wet or Dry |
|||||
Size (AWG or kcmil) |
N/A 8 | N/A 6 | N/A 4 | N/A 2 | N/A 1 | |||||
Stranding | N/A 7/W | N/A 7/W | N/A 7/W | N/A 7/W | N/A 18/w | |||||
Insulation Thickness (mils) |
N/A 60 mls | N/A 60 mls | N/A 60 mls | N/A 60 mls | N/A 80 mls | |||||
Outside Diameter |
N/A .266 Inches | N/A .290 Inches | N/A .334 Inches | N/A .390 Inches | N/A .460 Inches | |||||
Weight (lb/1000 ft) |
N/A 37 Lbs | N/A 49 Lbs | N/A 65 Lbs | N/A 94 Lbs | N/A 125 Lbs | |||||
Ampacity 90 ºC |
N/A 45 Amps | N/A 60 Amps | N/A 75 Amps | N/A 100 Amps | N/A 115 Amps | |||||
|