Bare Copper - Stranded
Bare and Tinned Copper
APPLICATIONS
Used for overhead electrical transmission and distribution lines, grounding electrical systems, electrical test equipment and other infrastructure.
CONSTRUCTION
Conductors: Concentric-lay stranded bare copper conductors available in soft, medium hard, or hard temper. Stranded tin coated copper conductors available in soft temper only.
STANDARDS
Used for overhead electrical transmission and distribution lines, grounding electrical systems, electrical test equipment and other infrastructure.
CONSTRUCTION
Conductors: Concentric-lay stranded bare copper conductors available in soft, medium hard, or hard temper. Stranded tin coated copper conductors available in soft temper only.
STANDARDS
- ASTM B1 - Hard-drawn copper wire
- ASTM B2 - Medium hard-drawn copper wire
- ASTM B3 - Soft or annealed copper wire
- ASTM B8 - Concentric-lay stranded copper conductors: all tempers
- ASTM B258 - Standard Specification for Standard Nominal Diameters and Cross-Sectional Areas of AWG Sizes of Solid Round Wires Used as Electrical Conductors
- Federal Specification QQ-W-343 - Wire, Electrical, Copper (Uninsulated)
NOTES
Dimensions and weights are nominal values, subject to standard manufacturing tolerances. Conductor ampacities are in accordance with the NEC, latest edition.
Updated 12/6/2021
Unit of Measure
Items |
/Asset/BARE-COPPER-WIRE.jpg 8-01BC7 Bare Copper - Stranded |
/Asset/BARE-COPPER-WIRE.jpg 6-01BC7 Bare Copper - Stranded |
/Asset/BARE-COPPER-WIRE.jpg 4-01BC7 Bare Copper - Stranded |
/Asset/BARE-COPPER-WIRE.jpg 3-01BC7 Bare Copper - Stranded |
/Asset/BARE-COPPER-WIRE.jpg 2-01BC7 Bare Copper - Stranded |
|||||
Item # Soft |
N/A 8-01BC700 | N/A 6-01BC700 | N/A 4-01BC700 | N/A 3-01BC700 | N/A 2-01BC700 | |||||
Item # Medium |
N/A 8-01BC710 | N/A 6-01BC710 | N/A 4-01BC710 | N/A 3-01BC710 | N/A 2-01BC710 | |||||
Item # Hard |
N/A 8-01BC720 | N/A 6-01BC720 | N/A 4-01BC720 | N/A 3-01BC720 | N/A 2-01BC720 | |||||
Size AWG or KCMIL |
N/A 8 | N/A 6 | N/A 4 | N/A 3 | N/A 2 | |||||
Number of Strands |
N/A 7/w | |||||||||
Overall Diameter |
N/A 0.146 Inches | N/A 0.184 Inches | N/A 0.232 Inches | N/A 0.260 Inches | N/A 0.292 Inches | |||||
Weight (lb/1000 ft) |
N/A 51.0 Lbs | N/A 81.1 Lbs | N/A 128.9 Lbs | N/A 162.50 Lbs | N/A 204.9 Lbs | |||||
Breaking Strength Soft |
N/A 499 Lbs | N/A 794 Lbs | N/A 1320 Lbs | N/A 1670.0 Lbs | N/A 2110 Lbs | |||||
Breaking Strength Medium |
N/A 610 Lbs | N/A 959 Lbs | N/A 1505 Lbs | N/A 1885.0 Lbs | N/A 2360 Lbs | |||||
Breaking Strength Hard |
N/A 777 Lbs | N/A 1228 Lbs | N/A 1938 Lbs | N/A 2433.0 Lbs | N/A 3050 Lbs | |||||
Allowable Ampacity |
N/A 95 Amps | N/A 130 Amps | N/A 170 Amps | N/A 200 Amps | N/A 230 Amps | |||||
|