Application

Type RHH, RHW-2 is suitable for use in free air, raceways or direct burial in accordance with NEC.  Applications include general purpose wiring for power distribution, services, feeders, and branch circuit wiring in residential, industrial, and commercial buildings

Construction

Conductor: Single copper conductor, stranded
Insulation: Heat resistant cross-linked polyethylene.  Temperature rating is 90°C in wet and dry applications
Packaging:  All produced or cut-to-order material will be shipped on non-returnable wooden reels unless specifically requested.

Standards 

  • ASTM B3, B8 and B787
  • UL 44 ICEA S-95-658/NEMA WC-70
  • For CT use 1/0 AWG and larger
  • Gasoline and Oil Resistant II
  • -40°C rated to 90°C in wet and dry applications
  • C(UL) US RWU90 1kV:CSA/UL Listed
  • C(UL) RPVU90 1kV
  • Sunlight Resistant
  • RoHS Compliant
Notes

*Based on ambient temperature of 30°C per NEC-Table 310-17

†The overcurrent protection for items marked with an obelisk (†) shall not exceed 15 amps for #14 AWG, 20 amps for #12 AWG, and 30 amps for #10 AWG per NEC 310-17 footnote.

Data shown is approximate and subject to standard industry tolerances.

Items
RHH/RHW-2 CT Rated 2kV CU

CU UL RHH/RHW-2 USE-2 2kV

RHH/RHW-2 CT Rated 2kV CU

CU UL RHH/RHW-2 USE-2 2kV

RHH/RHW-2 CT Rated 2kV CU

CU UL RHH/RHW-2 USE-2 2kV

RHH/RHW-2 CT Rated 2kV CU

CU UL RHH/RHW-2 USE-2 2kV

RHH/RHW-2 CT Rated 2kV CU

CU UL RHH/RHW-2 USE-2 2kV
Stranding N/A 7
Size
AWG
or
KCMIL
N/A 14 N/A 12 N/A 10 N/A 8 N/A 6
Insulation
Thickness
(mils)
N/A 60 N/A 60 N/A 60 N/A 80 N/A 80
Nominal
Overall
Diameter
(in)
N/A 0.193 N/A 0.212 N/A 0.236 N/A 0.306 N/A 0.344
Approximate
Net Weight
(lb/MFT)
N/A 27 N/A 37 N/A 51 N/A 83 N/A 120
Ampacity*
90°C
Wet/Dry
N/A 35† N/A 40† N/A 55† N/A 80 N/A 105