Type MP-GC 3-Conductor - EPR/CPE or XLP/CPE 8kV 100% Insulation Level (Grounded) 90°C
Type MP-GC (Mine Power Feeder)
Applications
This cable is designed for high voltage connections between power distribution systems in mines, mine tunnels, shafts, and mine load centers where continuous monitoring of the ground system is required. This cable is suitable for installation in Ducts, troughs, tray or direct burial for non-flexing service.
Construction
Conforms to ICEA S-66-524 (NEMA WC8).
Notes
This cable is designed for high voltage connections between power distribution systems in mines, mine tunnels, shafts, and mine load centers where continuous monitoring of the ground system is required. This cable is suitable for installation in Ducts, troughs, tray or direct burial for non-flexing service.
Construction
- Conductor is stranded annealed copper enveloped in a strand shield.
- Insulation is Ethylene Propylene Rubber (EPR) or Cross Linked Polyethylene (XLPE).
- Assembly is semi-conducting tape and a metallic tape shield with grounding conductors consisting of two bare grounds and one 8-gauge insulated ground check that are cabled together in the interstices of the power conductors and fillers are added to make round.
- A single faced rubber filled tape is applied overlapped.
- Jacket is Chlorinated Polyethylene (CPE).
Conforms to ICEA S-66-524 (NEMA WC8).
Notes
- Shipping tolerance +/- 10%
Unit of Measure
Items |
/ImgCustom/1006/placeholder_notavailable.gif MP8-01-4 Type MP-GC 3-Conductor - EPR/CPE or XLP/CPE 8kV 100% Insulation Level (Grounded) 90°C |
/ImgCustom/1006/placeholder_notavailable.gif MP8-02-2 Type MP-GC 3-Conductor - EPR/CPE or XLP/CPE 8kV 100% Insulation Level (Grounded) 90°C |
/ImgCustom/1006/placeholder_notavailable.gif MP8-03-1 Type MP-GC 3-Conductor - EPR/CPE or XLP/CPE 8kV 100% Insulation Level (Grounded) 90°C |
/ImgCustom/1006/placeholder_notavailable.gif MP8-04-1/0 Type MP-GC 3-Conductor - EPR/CPE or XLP/CPE 8kV 100% Insulation Level (Grounded) 90°C |
/ImgCustom/1006/placeholder_notavailable.gif MP8-05-2/0 Type MP-GC 3-Conductor - EPR/CPE or XLP/CPE 8kV 100% Insulation Level (Grounded) 90°C |
|||||
Power Conductors Size AWG |
N/A 4 | N/A 2 | N/A 1 | N/A 1/0 | N/A 2/0 | |||||
Power Conductors # of Strands |
N/A 7 | N/A 7 | N/A 19 | N/A 19 | N/A 19 | |||||
Power Conductors Insulation Thickness |
N/A 0.115 Inches | |||||||||
Ground Wire Size AWG |
N/A 8 | N/A 6 | N/A 5 | N/A 4 | N/A 3 | |||||
Ground Wire # of Strands |
N/A 7 | |||||||||
Jacket Thickness (Inches) |
N/A 0.11 | N/A 0.11 | N/A 0.11 | N/A 0.11 | N/A 0.14 | |||||
Overall Diameter (inches) |
N/A 1.43 | N/A 1.55 | N/A 1.65 | N/A 1.75 | N/A 1.88 | |||||
Net Weight Per MFT |
N/A 1440 Lbs | N/A 1760 Lbs | N/A 2070 Lbs | N/A 2440 Lbs | N/A 2940 Lbs | |||||
|