Applications
Stranded 1350 aluminum conductors shown in this section of data are classified as follows:
Class AA For bare conductors usually used in overhead lines.
Class A For conductors to be covered with weather-resistant materials and for bare conductors where greater flexibility is required.
Compact strand conductor for use in bare overhead applications or for use with weather-resistant coverings or insulations is also available.
Classes refer to stranding and are an indication of relative conductor flexibility, AA being the least flexible, C the most flexible.
Construction
Aluminum alloy 1350-H19 wires, concentrically stranded.
Specifications
AAC bare conductors meet or exceed the following ASTM specifications :
B-230 Aluminum Wire, 1350-H19 for Electrical Purposes
B-231 Aluminum Conductors, Concentric-Lay-Stranded
B-400Compact Round Concentric-Lay-Stranded Aluminum 1350 Conductors
Notes
Stranded 1350 aluminum conductors shown in this section of data are classified as follows:
Class AA For bare conductors usually used in overhead lines.
Class A For conductors to be covered with weather-resistant materials and for bare conductors where greater flexibility is required.
Compact strand conductor for use in bare overhead applications or for use with weather-resistant coverings or insulations is also available.
Classes refer to stranding and are an indication of relative conductor flexibility, AA being the least flexible, C the most flexible.
Construction
Aluminum alloy 1350-H19 wires, concentrically stranded.
Specifications
AAC bare conductors meet or exceed the following ASTM specifications :
B-230 Aluminum Wire, 1350-H19 for Electrical Purposes
B-231 Aluminum Conductors, Concentric-Lay-Stranded
B-400
Notes
- Resistance is calculated using ASTM standard increments of stranding and metal conductivity of 52.5% IACS, AC resistance at 60Hz
- Current ratings are based on 75 ºC conductor temperature, 25 ºC ambient, 2ft/s wind, 96/watts/sq.ft sun, .05 coefficients of emissivity and absorption.
Unit of Measure
Specifications
Code Name |
N/A Pansy |
Size
|
N/A 1 |
No. of Wires |
N/A 7 |
CLASS |
N/A A AA |
Diameter
|
N/A 0.1093 Inches |
Diameter
|
N/A 0.328 Inches |
Cross
|
N/A 0.0657 sq.inches |
Weight
|
N/A 99.1 Lbs |
Rated
|
N/A 1640 Lbs |
Resistance
|
N/A 0.207 Ω |
Resistance
|
N/A 0.252 Ω |
Rating |
N/A 214 Amps |
Standard Package Length (Feet) |
N/A 2550 ft.8915 ft.17830 ft. |
Standard Package Weight (Lbs.) |
N/A 200 Lbs700 Lbs1400 Lbs |
Reel Size |
N/A Coil NR 36.22 NR 42.28 |