Applications

This cable is intended for fixed installation in wind turbine towers. Good resistance to temperatures, oils, ozone and fire. This cable is intended for use in solar power generation applications to connect the inverter to transformer where high flexibility is required, commonly applied to prefabricated inverter and transformer skids.  Additionally, this cable is appropriate for tight battery applications, as well as superior alternatives to battery cable. TOWERGUARD CCA®  can also be used for secondary voltage resistance welding leads and in power supply applications not exceeding 2000V volts.

Construction
Nominal voltage: RHH or RHW-2 2000V UL
Conductor: The conductor shall be a flexible Copperclad Aluminum (CCA), an electrical conductor that has an outer sleeve of copper metallurgically bonded to a solid aluminum core. The combination of these two metals makes it uniquely suited to many electrical applications where weights to electrical conductivity issues are important. This bimetallic wire is much lighter than copper and only slightly heavier than bare aluminum. The density of CCA is about 35% lighter than copper. CCA conducts like copper for AC frequencies. This product meets or exceeds the minimum requirements set forth in ASTM B 566 04.
Separator: A suitable tape separator between the conductor and insulation.
Insulation: Ethylene-propylene rubber (EPR) type EP, meeting UL and ICEA requirements for 90ºC.
Jacket: A heavy duty, thermosetting CPE in accordance with ICEA S-95-658 NEMA WC70 or optional Low Smoke Zero Halogen jacket LSZH.
Jacket Color: Black
Print Legend: TOWERGUARD CCA® (SIZE AWG OR KCMIL) CU CLAD AL UL 217923 RHH or RHW-2 2000V SUN RES OIL RES U.S. Patent No. 8,618,688 (SEQUENTIAL FOOTAGE MARKER)

Specifications

  • ICEA S-95-658 / NEMA WC70
  • UL Standard 44
  • ASTM B 566
  • ASTM B 172
Product Features
  • 35% less expensive than copper cables with equal ampacity
  • Flexible cable design - TOWERGUARD CCA® can bend to a radius of 6 times the O.D. without impairing the insulation.
  • 90 ºC (dry) 90 ºC (wet)
  • Ozone, sunlight, oil, grease, weather, water, chemical and abrasion resistant jacket
  • Surface printed for easy identification
  • 35% lighter weight and easier to install than copper cables with equal ampacity
  • No scrap value (theft deterrent)
  • Sequential footage markers
  • U.S. Patent No. 8,618,688

Terminals and Splices
Testing has been completed using TOWERGUARD CCA® with BURNDY® aluminum HYLUG™ terminals and HYLINK™ splices. Both are UL Listed for use on copper clad aluminum cable. 
Click HERE to view a chart of cable sizes and corresponding Burndy part numbers in PDF format.



*Ampacity is calculated based on ambient air temperature of 30ºC, per 2008 NEC, Table 310-17
**Ampacity is calculated based on ambient air temperature of 30ºC, not more than three current-carrying conductors in raceway, cable, or earth, per 2008 NEC, Table 310-16

† Actual shipping weight may vary.

Conductor
Cross-
Sectional
Area
AWG/kcmil

N/A 500

Conductor
Nominal
No.
of
wires

N/A 779

Conductor
Overall
Diameter
Approximate
(inches)

N/A 0.91

Average
Insulation
Thickness
(mils)

N/A 75

Average
Jacket
Thickness
(mils)

N/A 65

Nominal
Cable
Diameter

N/A 1.19

Ampacity*
90 ºC
Free Air

N/A 545

Ampacity**
90 ºC
Duct

N/A 350

Corresponding
Size
of
DLO(CU)
AWG/kcmil

N/A 313

Net
Cable
Weight†
lbs/MFT

N/A 934