For information on conductor sizes or voltage ratings not shown in the tables, contact your AWG sales representative.
Dimensions and weights not designated minimum or maximum are nominal values and subject to manufacturing tolerances. In this context, weight means mass.
Items |
A1/0-01MV35UT10501 PowerGuard® 35kV 133% Shielded Power Cable AL Conductor 420 mils TRXLPE Copper Tape PVC Jacket |
A2/0-01MV35UT10501 PowerGuard® 35kV 133% Shielded Power Cable AL Conductor 420 mils TRXLPE Copper Tape PVC Jacket |
A3/0-01MV35UT10501 PowerGuard® 35kV 133% Shielded Power Cable AL Conductor 420 mils TRXLPE Copper Tape PVC Jacket |
A4/0-01MV35UT10501 PowerGuard® 35kV 133% Shielded Power Cable AL Conductor 420 mils TRXLPE Copper Tape PVC Jacket |
A250-01MV35UT10501 PowerGuard® 35kV 133% Shielded Power Cable AL Conductor 420 mils TRXLPE Copper Tape PVC Jacket |
|||||
Compressed Conductor Aluminum Size/ # of Wires |
N/A 1/0 / 19 | N/A 2/0 / 19 | N/A 3/0 / 19 | N/A 4/0 / 19 | N/A 250 / 37 | |||||
Nominal Insulation Thickness (mil) |
N/A 420 | |||||||||
Diameter Insulation MIN. (in.)1 |
N/A 1.198 | N/A 1.242 | N/A 1.292 | N/A 1.348 | N/A 1.394 | |||||
Diameter Insulation MAX. (in.)1 |
N/A 1.318 | N/A 1.362 | N/A 1.412 | N/A 1.468 | N/A 1.514 | |||||
Diameter 5 mil CU Tape (in.)1 |
N/A 1.318 | N/A 1.362 | N/A 1.412 | N/A 1.468 | N/A 1.514 | |||||
Diameter PVC Jacket (in.)1 |
N/A 1.478 | N/A 1.522 | N/A 1.572 | N/A 1.628 | N/A 1.674 | |||||
Nominal Jacket Thickness (in.)1 |
N/A 0.08 | |||||||||
Approximate Weight AL Conductor (lbs/MFT)1 |
N/A 99 | N/A 125 | N/A 158 | N/A 199 | N/A 234 | |||||
Approximate Weight CU Shield (lbs/MFT)1 |
N/A 92 | N/A 95 | N/A 99 | N/A 104 | N/A 108 | |||||
Approximate Weight Total Conductor (lbs/MFT)1 |
N/A 967 | N/A 1032 | N/A 1109 | N/A 1200 | N/A 1381 | |||||
Ampacity2 Direct Buried |
N/A 210 | N/A 240 | N/A 275 | N/A 310 | N/A 345 | |||||
Ampacity2 In Duct |
N/A 170 | N/A 190 | N/A 220 | N/A 250 | N/A 275 | |||||
|