Print Back
Application:
Mobile Home Feeder Cable is mainly used for supplying the energy required within the mobile home. The cable is designed for use at 600 volts or less and conductor temperatures not exceeding 90ºC.

Construction:
Quadruplex type USE-2 or RHH or RHW-2 compact stranded AA-8000 Series aluminum alloy conductors. Insulation is sunlight-resistant Cross-linked Polyethylene (XLPE). Neutral is identified by triple extruded white stripes and grounding is identified by total green surface coating.

Print Legend:
  • Manufacturer's ID plus E FILE NUMBER (SIZE AWG) AA-8000 AL TYPE USE-2 OR RHH OR RHW-2 SUN-RES 600V XLPE (UL) plus YEAR OF MANUFACTURE.
  • Sequential footage markings.

Installation:
Suitable for direct burial or underground installations and in raceways.

Standards
Mobile Home Feeder cable meets or exceeds the following specifications:
    • ASTM B800 and B801 or B836 as applicable.
    • Federal Specification A-A59544
  • UL 44
  • UL 854
  • NEC requirements.
To determine correct ampacity by conductor size, please consult the National Electric Code, the latest edition.
AL Mobile Home Feeder
Unit of Measure
Items AL Mobile Home Feeder
A2-04MHF01
Mobile Home Feeder - Aluminum Conductor
AL Mobile Home Feeder
A2-04MHF00
Mobile Home Feeder - Aluminum Conductor
AL Mobile Home Feeder
A2-04MHF00
Mobile Home Feeder - Aluminum Conductor
AL Mobile Home Feeder
A2/0-04MHF00
Mobile Home Feeder - Aluminum Conductor
AL Mobile Home Feeder
A4/0-04MHF01
Mobile Home Feeder - Aluminum Conductor
Cable
Description
N/A 2-2-4-6 N/A 2-2-2-4 N/A 2/0-2/0-1-4 N/A 2/0-2/0-2/0-1 N/A 4/0-4/0-2/0-4
Phase
Conductor
Size (AWG/KCMIL)
N/A 2 N/A 2 N/A 2/0 N/A 2/0 N/A 4/0
Phase
Conductor
XLP
Thickness
N/A 0.060 N/A 0.060 N/A 0.080 N/A 0.080 N/A 0.080
Phase
Conductor
O.D.
N/A 0.399 N/A 0.399 N/A 0.550 N/A 0.550 N/A 0.648
Neutral
Conductor
Size (AWG/KCMIL)
N/A 4 N/A 2 N/A 1 N/A 2/0 N/A 2/0
Neutral
Conductor
XLP
Thickness
N/A 0.060 N/A 0.060 N/A 0.080 N/A 0.080 N/A 0.080
Neutral
Conductor
O.D.
N/A 0.340 N/A 0.399 N/A 0.470 N/A 0.550 N/A 0.550
Ground
Cable
Size (AWG/KCMIL)
N/A 6 N/A 4 N/A 4 N/A 1 N/A 6
Ground
Cable
XLP
Thickness
N/A 0.060 N/A 0.060 N/A 0.060 N/A 0.080 N/A 0.060
Ground
Cable
O.D.
N/A 0.295 N/A 0.340 N/A 0.340 N/A 0.470 N/A 0.340
Finished
Cable
O.D.
N/A 0.950 N/A 0.950 N/A 1.308 N/A 1.308 N/A 1.550
Finished
Cable
Weight
(lbs/MFT)
N/A 310 N/A 357 N/A 569 N/A 683 N/A 797
Finished
Cable
Allowable
Ampacities
(75°)