Insulation Temperature Rating | |
Normal | 90º C |
Emergency* | 130 ºC |
Short Circuit - Shield | 200º C |
Short Circuit - Conductor | 250º C |
Items |
A1/0-01UD35GT000J PowerGuard® 35kV 100% MV 345 Mil TR-XLPE AL Collection System Cable LLDPE Jacket Concentric Neutral UL MV-90/AEIC CS8-07 - ELECTRICAL PROPERTIES |
A1/0-01UD35GT200J PowerGuard® 35kV 100% MV 345 Mil TR-XLPE AL Collection System Cable LLDPE Jacket Concentric Neutral UL MV-90/AEIC CS8-07 - ELECTRICAL PROPERTIES |
A1/0-01UD35GT001J PowerGuard® 35kV 100% MV 345 Mil TR-XLPE AL Collection System Cable LLDPE Jacket Concentric Neutral UL MV-90/AEIC CS8-07 - ELECTRICAL PROPERTIES |
A1/0-01UD35GT100J PowerGuard® 35kV 100% MV 345 Mil TR-XLPE AL Collection System Cable LLDPE Jacket Concentric Neutral UL MV-90/AEIC CS8-07 - ELECTRICAL PROPERTIES |
A2/0-01UD35GT100J PowerGuard® 35kV 100% MV 345 Mil TR-XLPE AL Collection System Cable LLDPE Jacket Concentric Neutral UL MV-90/AEIC CS8-07 - ELECTRICAL PROPERTIES |
|||||
Neutral Size |
N/A Full | N/A 2/3 | N/A 1/2 | N/A 1/3 | N/A Full | |||||
Conductor AL Size AWG or kcmil |
N/A 1/0 | N/A 1/0 | N/A 1/0 | N/A 1/0 | N/A 2/0 | |||||
TREFOIL ________ Pos/Neg Seq Impedance (µΩ/feet) |
N/A 238.93+52.77J | N/A 238.34+52.87J | N/A 237.98+52.91J | N/A 237.74+52.94J | N/A 185.36+50.32J | |||||
TREFOIL ________ Zero Seq Impedance (µΩ/feet) |
N/A 414.16+80.96J | N/A 475+125.63J | N/A 528.44+186.95J | N/A 568.18+262.76J | N/A 331.22+64.01J | |||||
TREFOIL ________ Ampacity LF=100% |
N/A 189 | N/A 189 | N/A 189 | N/A 189 | N/A 218 | |||||
TREFOIL ________ Ampacity LF=75% |
N/A 216 | N/A 216 | N/A 216 | N/A 216 | N/A 250 | |||||
FLAT SPACED @7.5 INCHES ________ Pos/Neg Seq Impedance (µΩ/feet) |
N/A 255.14+89.92J | N/A 249.93+93.18J | N/A 246.36+94.7J | N/A 243.83+95.49J | N/A 204.16+84.73J | |||||
FLAT SPACED @7.5 INCHES ________ Zero Seq Impedance (µΩ/feet) |
N/A 406.85+84.39J | N/A 461.51+130.24J | N/A 506.38+190.72J | N/A 536.16+262.11J | N/A 326.39+66.72J | |||||
FLAT SPACED @7.5 INCHES ________ Ampacity LF=100% |
N/A 206 | N/A 207 | N/A 208 | N/A 209 | N/A 236 | |||||
FLAT SPACED @7.5 INCHES ________ Ampacity LF=75% |
N/A 231 | N/A 232 | N/A 233 | N/A 234 | N/A 266 | |||||
FLAT SPACED TOUCHING ________ Pos/Neg Seq Impedance (µΩ/feet) |
N/A 239.58+57.07J | N/A 238.6+58J | N/A 237.89+58.14J | N/A 237.41+58.22J | N/A 186.83+55.29J | |||||
FLAT SPACED TOUCHING ________ Zero Seq Impedance (µΩ/feet) |
N/A 412.25+81.12J | N/A 472.2+125.83J | N/A 524.64+186.91J | N/A 563.28+262.11J | N/A 329.78+64.21J | |||||
FLAT SPACED TOUCHING ________ Ampacity LF=100% |
N/A 189 | N/A 189 | N/A 189 | N/A 189 | N/A 218 | |||||
FLAT SPACED TOUCHING ________ Ampacity LF=75% |
N/A 216 | N/A 216 | N/A 216 | N/A 216 | N/A 250 | |||||
Conductor Size AWG or kcmil |
N/A | |||||||||
Neutral Wires |
N/A | |||||||||
Neutral Size AWG |
N/A | |||||||||
Sequence Impedance Pos/Neg (µΩ/feet) |
N/A | |||||||||
Seq Impedance Zero (µΩ/feet) |
N/A | |||||||||
Sequence Impedance Pos/Neg (µΩ/feet) |
N/A | |||||||||
|