Applications
Construction
Conductor: Class A or B Compressed concentric stranded copper conductor. Optional water-blocking.
Conductor Shield: Extruded thermosetting semiconducting shield which is free stripping from the conductor and bonded to the insulation
Insulation: Extruded, unfilled Tree-Retardant Cross-linked Polyethylene (TRXLPE) as defined in ANSI/ICEA S-94-649
Insulation Shield: Extruded thermosetting semiconducting shield with controlled adhesion to the insulation providing the required balance between electrical integrity and ease of stripping.
Metallic Shield: The metallic shield is flat uncoated 5-mil thick copper tape helically applied with minimum 20% overlap
Ground Wire: Three bare copper ground wires placed at the interstice of the conductor.
Fillers: Non hygroscopic fillers, forming a firm and cylindrical cable core.
Binder Tape: A binder tape is applied to maintain core symmetry and mechanical stability.
Armor: Aluminum Interlocked Armor applied over the binder tape of the cable core
Jacket: Black, sunlight resistant, flame retardant PVC jacket
Specifications
Items |
2-03AIAPC15UT105 PowerGuard® Armored 15kV 133% CU 3/C with CU Ground Wire TR-XLPE Insulation CU Tape Shield AIA PVC Jacket UL Type MV-105 or MC, AEIC CS8 |
1-03AIAPC15UT105 PowerGuard® Armored 15kV 133% CU 3/C with CU Ground Wire TR-XLPE Insulation CU Tape Shield AIA PVC Jacket UL Type MV-105 or MC, AEIC CS8 |
1/0-03AIAPC15UT105 PowerGuard® Armored 15kV 133% CU 3/C with CU Ground Wire TR-XLPE Insulation CU Tape Shield AIA PVC Jacket UL Type MV-105 or MC, AEIC CS8 |
2/0-03AIAPC15UT105 PowerGuard® Armored 15kV 133% CU 3/C with CU Ground Wire TR-XLPE Insulation CU Tape Shield AIA PVC Jacket UL Type MV-105 or MC, AEIC CS8 |
3/0-03AIAPC15UT105 PowerGuard® Armored 15kV 133% CU 3/C with CU Ground Wire TR-XLPE Insulation CU Tape Shield AIA PVC Jacket UL Type MV-105 or MC, AEIC CS8 |
|||||
Size AWG or KCMIL |
N/A 2 | N/A 1 | N/A 1/0 | N/A 2/0 | N/A 3/0 | |||||
Insulation Thickness (mil) |
N/A 220 | |||||||||
No. of Ground Wires |
N/A 3 | |||||||||
Size AWG of Ground Wires |
N/A 10 | N/A 8 | N/A 8 | N/A 8 | N/A 7 | |||||
Conductor Diameter (in) |
N/A 0.266 | N/A 0.299 | N/A 0.341 | N/A 0.376 | N/A 0.423 | |||||
Insulation Diameter (in) |
N/A 0.76 | N/A 0.79 | N/A 0.83 | N/A 0.87 | N/A 0.92 | |||||
Insulation Shield Diameter (in) |
N/A 0.82 | N/A 0.85 | N/A 0.89 | N/A 0.93 | N/A 0.97 | |||||
Overall Jacket Diameter (in) |
N/A 2.19 | N/A 2.26 | N/A 2.35 | N/A 2.45 | N/A 2.55 | |||||
Approximate Weight (lb/MFT) |
N/A 2406 | N/A 2647 | N/A 2962 | N/A 3437 | N/A 3886 | |||||
Minimum Bending Radius (in) |
N/A 16 | N/A 16 | N/A 17 | N/A 18 | N/A 18 | |||||
Ampacity 105ºC in Duct |
N/A 160 | N/A 185 | N/A 210 | N/A 235 | N/A 270 | |||||
Ampacity 105ºC in Air |
N/A 185 | N/A 210 | N/A 240 | N/A 275 | N/A 315 | |||||
|