Applications
Construction
Conductor: Class A or B Compressed concentric stranded copper conductor. Optional water-blocking.
Conductor Shield: Extruded thermosetting semiconducting shield which is free stripping from the conductor and bonded to the insulation
Insulation: Extruded, unfilled Tree-Retardant Cross-linked Polyethylene (TRXLPE) as defined in ANSI/ICEA S-94-649
Insulation Shield: Extruded thermosetting semiconducting shield with controlled adhesion to the insulation providing the required balance between electrical integrity and ease of stripping.
Metallic Shield: The metallic shield is flat uncoated 5-mil thick copper tape helically applied with minimum 20% overlap
Ground Wire: Three bare copper ground wires placed at the interstice of the conductor.
Fillers: Non hygroscopic fillers, forming a firm and cylindrical cable core.
Binder Tape: A binder tape is applied to maintain core symmetry and mechanical stability.
Armor: Aluminum Interlocked Armor applied over the binder tape of the cable core
Jacket: Black, sunlight resistant, flame retardant PVC jacket
Specifications
Items |
1-03AIAPC25GT105 PowerGuard® Armored 25kV 100% CU 3/C with CU Ground Wire TR-XLPE Insulation CU Tape Shield AIA PVC Jacket UL Type MV-105 or MC, AEIC CS8 |
1/0-03AIAPC25GT105 PowerGuard® Armored 25kV 100% CU 3/C with CU Ground Wire TR-XLPE Insulation CU Tape Shield AIA PVC Jacket UL Type MV-105 or MC, AEIC CS8 |
2/0-03AIAPC25GT105 PowerGuard® Armored 25kV 100% CU 3/C with CU Ground Wire TR-XLPE Insulation CU Tape Shield AIA PVC Jacket UL Type MV-105 or MC, AEIC CS8 |
3/0-03AIAPC25GT105 PowerGuard® Armored 25kV 100% CU 3/C with CU Ground Wire TR-XLPE Insulation CU Tape Shield AIA PVC Jacket UL Type MV-105 or MC, AEIC CS8 |
4/0-03AIAPC25GT105 PowerGuard® Armored 25kV 100% CU 3/C with CU Ground Wire TR-XLPE Insulation CU Tape Shield AIA PVC Jacket UL Type MV-105 or MC, AEIC CS8 |
|||||
Size AWG or KCMIL |
N/A 1 | N/A 1/0 | N/A 2/0 | N/A 3/0 | N/A 4/0 | |||||
Insulation Thickness (mil) |
N/A 260 | |||||||||
No. of Ground Wires |
N/A 3 | |||||||||
Size AWG of Ground Wires |
N/A 8 | N/A 8 | N/A 8 | N/A 7 | N/A 7 | |||||
Conductor Diameter (in) |
N/A 0.299 | N/A 0.341 | N/A 0.376 | N/A 0.423 | N/A 0.479 | |||||
Insulation Diameter (in) |
N/A 0.87 | N/A 0.91 | N/A 0.95 | N/A 1 | N/A 1.05 | |||||
Insulation Shield Diameter (in) |
N/A 0.93 | N/A 0.97 | N/A 1.01 | N/A 1.07 | N/A 1.13 | |||||
Overall Jacket Diameter (in) |
N/A 2.46 | N/A 2.55 | N/A 2.63 | N/A 2.76 | N/A 2.88 | |||||
Approximate Weight (lb/MFT) |
N/A 2991 | N/A 3319 | N/A 3735 | N/A 4260 | N/A 4827 | |||||
Minimum Bending Radius (in) |
N/A 18 | N/A 18 | N/A 19 | N/A 20 | N/A 21 | |||||
Ampacity 105ºC in Duct |
N/A 185 | N/A 210 | N/A 235 | N/A 270 | N/A 305 | |||||
Ampacity 105ºC in Air |
N/A 210 | N/A 240 | N/A 275 | N/A 315 | N/A 360 | |||||
|