The rating of the overcurrent device shown above is in accordance with the NEC® for single runs. See 240.4 and 240.6. Also, see 110.14 and Table 310.15(B)16 of the NEC.
Items |
A6-03AIA-WG-600V Three Conductor Aluminum Jacketed MC Cable and Grounding Conductor 600V |
A4-03AIA-WG-600V Three Conductor Aluminum Jacketed MC Cable and Grounding Conductor 600V |
A2-03AIA-WG-600V Three Conductor Aluminum Jacketed MC Cable and Grounding Conductor 600V |
A1-03AIA-WG-600V Three Conductor Aluminum Jacketed MC Cable and Grounding Conductor 600V |
A1/0-03AIA-WG-600V Three Conductor Aluminum Jacketed MC Cable and Grounding Conductor 600V |
|||||
Conductor Size (AWG/KCMIL) |
N/A 6 | N/A 4 | N/A 2 | N/A 1 | N/A 1/0 | |||||
No. of Phase Conductors |
N/A 3 | |||||||||
Grounding Conductor Size (AWG/KCMIL) |
N/A 6 | N/A 6 | N/A 6 | N/A 4 | N/A 4 | |||||
Diameter of Conductor Assembly Under Armor (Inches) |
N/A 0.61 | N/A 0.68 | N/A 0.77 | N/A 0.90 | N/A 0.96 | |||||
Diameter of Cable Over Armor (Inches) |
N/A 0.83 | N/A 0.09 | N/A 1.00 | N/A 1.12 | N/A 1.18 | |||||
Overall Finished Diameter of Cable (Inches) |
N/A 0.93 | N/A 1.00 | N/A 1.09 | N/A 1.22 | N/A 1.28 | |||||
Cable Weight (LBS/MFT) |
N/A 312 | N/A 380 | N/A 482 | N/A 595 | N/A 691 | |||||
Rating of OC Device @ 75°C (AMPS) |
N/A 50 | N/A 70 | N/A 90 | N/A 100 | N/A 125 | |||||
Rated Ampacity @ 75°C (AMPS) |
N/A 50 | N/A 65 | N/A 90 | N/A 100 | N/A 120 | |||||
|