PowerGuard® AL 35kV 100% TR-XLPE CN XLPE UL Type MV-105 - Physical Properties (Compact)

APPLICATIONS
PowerGuard®-XL cables are intended for use in wet or dry locations for distribution of single or three phase medium- voltage power. These cables may be installed in ducts, exposed to sunlight or direct buried.

CONSTRUCTION
Single conductor cable with filled strand aluminum conductors, true triple extrusion, dry cured insulation system consisting of a thermosetting semiconducting conductor shield, high dielectric strength PowerGuard®-XL tree-retardant cross-linked polyethylene (TR-XLPE) insulation, thermosetting semiconducting insulation shield, copper concentric neutral wires, water blocking agents, black encapsulating cross-linked polyethylene (XLPE) jacket.

Conductor:
1000 kcmil and Smaller - Compact stranded aluminum alloy 1350.
Larger than 1000 kcmil - Compressed concentric stranded aluminum alloy 1350.
Stranded conductors are water-blocked with conductor filling compound.
Conductor Shield:
Extruded thermosetting semiconducting cross-linked polyethylene (XLPE) shield which is free stripping from the conductor and bonded to the insulation.
Insulation:
Extruded, Tree-Retardant Cross-linked Polyethylene (TR-XLPE) - 100% insulation level.
Insulation Shield:
Extruded thermosetting semiconducting cross-linked polyethylene (XLPE) shield with controlled adhesion to the insulation providing the required balance between electrical integrity and ease of stripping.
Metallic Shield:
Solid bare annealed copper wires helically applied and uniformly spaced.
Water-blocking agents:
Applied over the insulation shield and around the concentric neutral wires to resist longitudinal water penetration. Longitudinal water penetration shall be tested in accordance with the latest edition of ICEA T-34-664 except that the minimum requirement is 15 psig for 1 hour.
Outer jacket:
An extruded-to-fill black non-conducting cross-linked polyethylene (XLPE) jacket, meeting the physical requirements of Table 1, below, when tested by the methods specified in ANSI/ICEA S-94-649. The jacket shall be free-stripping and not interfere with an intimate contact between the neutral wires and theunderlying extruded insulation shield. The jacket is sunlight resistant and marked. The jacket shall contain a print legend marking, sequential length (meter or feet) marking and three longitudinal extruded red stripes. 

Physical Properties of Extruded-to-Fill LLDPE Jacket
Unaged Tensile Strength, minimum (PSI) 1500
Aged* Tensile Strength, minimum retention (%) 70
Unaged Elongated, minimum (%) 150
Aged* Elongated, minimum retention (%) 70
Heat Distortion 1 hr at 100ºC, maximum (%) 30
*Aged for 48 hrs at 100ºC

 

TEMPERATURE RATING  
Insulated Conductor and Shield Wire Temperature Ratings
Normal 105ºC
Emergency** 140ºC
Short-Circuit – Insulated Conductor 250ºC
Short-Circuit – Shield Wires 350ºC
**Operation at the emergency overload temperature shall not exceed 1500 hours cumulative during the lifetime of the cable.

 

STANDARDS
These cables are manufactured and tested to meet or exceed the following standards:

• ASTM B400 – Compact Round Concentric-Lay-Stranded Aluminum 1350Conductors
• ASTM B231 – Concentric-Lay-Stranded Aluminum 1350 Conductors
• ASTM B3 – Soft or Annealed Copper Wire
• ICEA S-94-649 – Concentric Neutral Cables Rated 5 Through 46 kV
• ICEA T-31-610 – Test Method for Conducting Longitudinal Water Penetration Resistance Tests on Blocked Conductors
• ICEA T-34-664 – Test Method for Conducting Longitudinal Water Penetration Resistance Tests on Longitudinal Water Blocked Cables
• ICEA P-45-482 – Short Circuit Performance of Metallic Shields and Sheaths on Insulated Cable
• AEIC CS8 – Extruded Dielectric, Shielded Power Cables Rated 5 Through 46 kV
• UL 1072 – Medium-Voltage Power Cables

LISTINGS AND CERTIFICATIONS

• UL listed as Type MV-105 – File E476447


NOTES

1. Dimensions and weights are subject to standard manufacturing tolerances and are subject to change without notice.

2. Cables are manufactured, tested and marked to meet or exceed the requirements in ANSI/ICEA S-94-649 for concentric neutral cables rated 5-46 kV and the latest revision of AEIC CS8.

3. Migration of soil moisture away from the cable is more likely at the higher operating conductor temperature and can result in an increase in soil thermal resistivity, resulting in an increase in conductor and soil temperature.



Updated 2/8/2022

AWG MV AL XLPE CU CN
Unit of Measure
1 

Item #

Conductor
Size
(AWG
or
kcmil)

Neutral
Size

Neutral
Wires

Neutral
Size
AWG

Diameter
Conductor
(in)

Diameter
Insulation
(in)

Diameter
Insulation
Shield
(in)

Diameter
Jacket
(in)

Weight
Aluminum
(lb/1000 ft)

Weight
Copper
(lb/1000 ft)

Weight
Net
(lb/1000 ft)

A1/0-01UD35GT101X N/A 1/0 N/A Full N/A 12 N/A 14 N/A 0.336 N/A 1.066 N/A 1.156 N/A 1.388 N/A 99.1 N/A 152 N/A 835
A1/0-01UD35GT203X N/A 1/0 N/A 2/3 N/A 13 N/A 16 N/A 0.336 N/A 1.066 N/A 1.156 N/A 1.362 N/A 99.1 N/A 104 N/A 765
A1/0-01UD35GT102X N/A 1/0 N/A 1/2 N/A 10 N/A 16 N/A 0.336 N/A 1.066 N/A 1.156 N/A 1.362 N/A 99.1 N/A 79.7 N/A 748
A1/0-01UD35GT103X N/A 1/0 N/A 1/3 N/A 7 N/A 16 N/A 0.336 N/A 1.066 N/A 1.156 N/A 1.362 N/A 99.1 N/A 55.8 N/A 720
A2/0-01UD35GT101X N/A 2/0 N/A Full N/A 15 N/A 14 N/A 0.376 N/A 1.106 N/A 1.196 N/A 1.428 N/A 125 N/A 190 N/A 925
A2/0-01UD35GT203X N/A 2/0 N/A 2/3 N/A 16 N/A 16 N/A 0.376 N/A 1.106 N/A 1.196 N/A 1.402 N/A 125 N/A 127 N/A 844
A2/0-01UD35GT102X N/A 2/0 N/A 1/2 N/A 12 N/A 16 N/A 0.376 N/A 1.106 N/A 1.196 N/A 1.402 N/A 125 N/A 95.6 N/A 816
A2/0-01UD35GT103X N/A 2/0 N/A 1/3 N/A 9 N/A 16 N/A 0.376 N/A 1.106 N/A 1.196 N/A 1.402 N/A 125 N/A 71.7 N/A 794
A3/0-01UD35GT101X N/A 3/0 N/A Full N/A 19 N/A 14 N/A 0.423 N/A 1.153 N/A 1.243 N/A 1.475 N/A 157 N/A 240 N/A 1035
A3/0-01UD35GT203X N/A 3/0 N/A 2/3 N/A 13 N/A 14 N/A 0.423 N/A 1.153 N/A 1.243 N/A 1.475 N/A 157 N/A 164 N/A 967
A3/0-01UD35GT102X N/A 3/0 N/A 1/2 N/A 15 N/A 16 N/A 0.423 N/A 1.153 N/A 1.243 N/A 1.449 N/A 157 N/A 119 N/A 901
A3/0-01UD35GT103X N/A 3/0 N/A 1/3 N/A 11 N/A 16 N/A 0.423 N/A 1.153 N/A 1.243 N/A 1.449 N/A 157 N/A 87.6 N/A 872
A4/0-01UD35GT101X N/A 4/0 N/A Full N/A 23 N/A 14 N/A 0.475 N/A 1.205 N/A 1.295 N/A 1.527 N/A 199 N/A 291 N/A 1165
A4/0-01UD35GT203X N/A 4/0 N/A 2/3 N/A 15 N/A 14 N/A 0.475 N/A 1.205 N/A 1.295 N/A 1.527 N/A 199 N/A 190 N/A 1070
A4/0-01UD35GT102X N/A 4/0 N/A 1/2 N/A 12 N/A 14 N/A 0.475 N/A 1.205 N/A 1.295 N/A 1.527 N/A 199 N/A 152 N/A 1035
A4/0-01UD35GT103X N/A 4/0 N/A 1/3 N/A 8 N/A 14 N/A 0.475 N/A 1.205 N/A 1.295 N/A 1.527 N/A 199 N/A 101 N/A 985
A250-01UD35GT203X N/A 250 N/A 2/3 N/A 19 N/A 14 N/A 0.52 N/A 1.258 N/A 1.348 N/A 1.58 N/A 235 N/A 240 N/A 1189
A250-01UD35GT102X N/A 250 N/A 1/2 N/A 14 N/A 14 N/A 0.52 N/A 1.258 N/A 1.348 N/A 1.58 N/A 235 N/A 177 N/A 1132
A250-01UD35GT103X N/A 250 N/A 1/3 N/A 10 N/A 14 N/A 0.52 N/A 1.258 N/A 1.348 N/A 1.58 N/A 235 N/A 126 N/A 1087
A250-01UD35GT106X N/A 250 N/A 1/6 N/A 8 N/A 16 N/A 0.52 N/A 1.258 N/A 1.348 N/A 1.554 N/A 235 N/A 63.7 N/A 1003
A350-01UD35GT203X N/A 350 N/A 2/3 N/A 16 N/A 12 N/A 0.616 N/A 1.354 N/A 1.444 N/A 1.766 N/A 329 N/A 323 N/A 1526
A350-01UD35GT102X N/A 350 N/A 1/2 N/A 20 N/A 14 N/A 0.616 N/A 1.354 N/A 1.444 N/A 1.732 N/A 329 N/A 253 N/A 1425
A350-01UD35GT103X N/A 350 N/A 1/3 N/A 13 N/A 14 N/A 0.616 N/A 1.354 N/A 1.444 N/A 1.732 N/A 329 N/A 164 N/A 1335
A350-01UD35GT106X N/A 350 N/A 1/6 N/A 11 N/A 16 N/A 0.616 N/A 1.354 N/A 1.444 N/A 1.706 N/A 329 N/A 87.6 N/A 1247
A500-01UD35GT203X N/A 500 N/A 2/3 N/A 23 N/A 12 N/A 0.736 N/A 1.474 N/A 1.594 N/A 1.916 N/A 469 N/A 465 N/A 1922
A500-01UD35GT102X N/A 500 N/A 1/2 N/A 18 N/A 12 N/A 0.736 N/A 1.474 N/A 1.594 N/A 1.916 N/A 469 N/A 364 N/A 1832
A500-01UD35GT103X N/A 500 N/A 1/3 N/A 12 N/A 12 N/A 0.736 N/A 1.474 N/A 1.594 N/A 1.916 N/A 469 N/A 242 N/A 1695
A500-01UD35GT106X N/A 500 N/A 1/6 N/A 10 N/A 14 N/A 0.736 N/A 1.474 N/A 1.594 N/A 1.882 N/A 469 N/A 126 N/A 1550
A750-01UD35GT102X N/A 750 N/A 1/2 N/A 17 N/A 10 N/A 0.908 N/A 1.654 N/A 1.774 N/A 2.138 N/A 704 N/A 544 N/A 2433
A750-01UD35GT103X N/A 750 N/A 1/3 N/A 18 N/A 12 N/A 0.908 N/A 1.654 N/A 1.774 N/A 2.096 N/A 704 N/A 364 N/A 2235
A750-01UD35GT106X N/A 750 N/A 1/6 N/A 14 N/A 14 N/A 0.908 N/A 1.654 N/A 1.774 N/A 2.062 N/A 704 N/A 177 N/A 2020
A750-01UD35GT112X N/A 750 N/A 1/12 N/A 11 N/A 16 N/A 0.908 N/A 1.654 N/A 1.774 N/A 2.036 N/A 704 N/A 87.6 N/A 1856
A1000-01UD35GT102X N/A 1000 N/A 1/2 N/A 22 N/A 10 N/A 1.06 N/A 1.806 N/A 1.926 N/A 2.29 N/A 938 N/A 705 N/A 2935
A1000-01UD35GT103X N/A 1000 N/A 1/3 N/A 23 N/A 12 N/A 1.06 N/A 1.806 N/A 1.926 N/A 2.248 N/A 938 N/A 465 N/A 2657
A1000-01UD35GT106X N/A 1000 N/A 1/6 N/A 12 N/A 12 N/A 1.06 N/A 1.806 N/A 1.926 N/A 2.248 N/A 938 N/A 242 N/A 2460
A1000-01UD35GT112X N/A 1000 N/A 1/12 N/A 10 N/A 14 N/A 1.06 N/A 1.806 N/A 1.926 N/A 2.214 N/A 938 N/A 126 N/A 2305
A1250-01UD35GT103X N/A 1250 N/A 1/3 N/A 18 N/A 10 N/A 1.25 N/A 2 N/A 2.12 N/A 2.484 N/A 1174 N/A 577 N/A 3218
A1250-01UD35GT106X N/A 1250 N/A 1/6 N/A 15 N/A 12 N/A 1.25 N/A 2 N/A 2.12 N/A 2.442 N/A 1174 N/A 303 N/A 2940
A1250-01UD35GT108X N/A 1250 N/A 1/8 N/A 12 N/A 12 N/A 1.25 N/A 2 N/A 2.12 N/A 2.442 N/A 1174 N/A 242 N/A 2851
A1250-01UD35GT112X N/A 1250 N/A 1/12 N/A 12 N/A 14 N/A 1.25 N/A 2 N/A 2.12 N/A 2.408 N/A 1174 N/A 152 N/A 2750
A1500-01UD35GT103X N/A 1500 N/A 1/3 N/A 22 N/A 10 N/A 1.37 N/A 2.12 N/A 2.24 N/A 2.604 N/A 1410 N/A 705 N/A 3667
A1500-01UD35GT106X N/A 1500 N/A 1/6 N/A 18 N/A 12 N/A 1.37 N/A 2.12 N/A 2.24 N/A 2.562 N/A 1410 N/A 364 N/A 3290
A1500-01UD35GT112X N/A 1500 N/A 1/12 N/A 14 N/A 14 N/A 1.37 N/A 2.12 N/A 2.24 N/A 2.528 N/A 1410 N/A 177 N/A 3067
Unit of Measure
1