UL Type MV-105 Ampacities - Aluminum Conductors - Rated 5 kV to 35 kV
UL Type MV-105 Ampacities - Aluminum Conductors - Rated 5 kV to 35 kV
Ampacity
Direct Buried
(Touching)
5 kV to 35 kVAmpacity
Direct Buried
(Spaced 7.5 in)
5 kV to 35 kVAmpacity
In Conduit In Air
(Touching)
5 kV to 35 kVAmpacity
In Cable Tray
(Spaced One
Cable Diameter)
5 kV to 15 kVAmpacity
In Cable Tray
(Spaced One
Cable Diameter)
25 kV to 35 kV2023 NEC Article Article 315.60(F) Article 315.60(F) Article 315.60(E) Article 392.80(B)(2)(2) Article 392.80(B)(2)(2) 2023 NEC Table Table 315.60(C)(20),
One CircuitTable 315.60(C)(16),
One CircuitTable 315.60(C)(8) Table 315.60(C)(4) Table 315.60(C)(4) Cable Configuration Figure 315.60(D)(3),
Detail 7Figure 315.60(D)(3),
Detail 9Touching Single Layer, Spaced One Cable Diameter Single Layer, Spaced One Cable Diameter Installation Conditions Earth Ambient
= 20 deg C (68 F)
Earth Thermal Resistivity
= 0.90 deg C m / W Depth of Burial = 36 inEarth Ambient
= 20 deg C (68 F)
Earth Thermal Resistivity
= 0.90 deg C m / W Depth of Burial = 36 inAmbient Air = 40 deg C (104 F) Ambient Air = 40 deg C (104 F) Ambient Air = 40 deg C (104 F)
-
UL Type MV-105 Ampacities - Copper Conductors - Rated 5 kV to 35 kV
UL Type MV-105 Ampacities - Copper Conductors - Rated 5 kV to 35 kV
Ampacity
Direct Buried
(Touching)
5 kV to 35 kVAmpacity
Direct Buried
(Spaced 7.5 in)
5 kV to 35 kVAmpacity
In Conduit In Air
(Touching)
5 kV to 35 kVAmpacity
In Cable Tray
(Spaced One
Cable Diameter)
5 kV to 15 kVAmpacity
In Cable Tray
(Spaced One
Cable Diameter)
25 kV to 35 kV2023 NEC Article Article 315.60(F) Article 315.60(F) Article 315.60(E) Article 392.80(B)(2)(2) Article 392.80(B)(2)(2) 2023 NEC Table Table 315.60(C)(19),
One CircuitTable 315.60(C)(165,
One CircuitTable 315.60(C)(7) Table 315.60(C)(3) Table 315.60(C)(3) Cable Configuration Figure 315.60(D)(3),
Detail 7Figure 315.60(D)(3),
Detail 9Touching Single Layer, Spaced One Cable Diameter Single Layer, Spaced One Cable Diameter Installation Conditions Earth Ambient
= 20 deg C (68 F)
Earth Thermal Resistivity
= 0.90 deg C m / W Depth of Burial = 36 inEarth Ambient
= 20 deg C (68 F)
Earth Thermal Resistivity
= 0.90 deg C m / W Depth of Burial = 36 inAmbient Air = 40 deg C (104 F) Ambient Air = 40 deg C (104 F) Ambient Air = 40 deg C (104 F)