Aluminum 600V Armored MC Cable XHHW-2
mored-cables-aluminum-600v-armored-mc-cable-xhhw-2
-
Type MC Three Conductor w/Ground Aluminum Armor XHHW-2 600V
Applications
Type MC Cable is primarily used for services, feeders, and branch circuits as specified in the 2011 National Electric Code. Type MC cable with Type XHHW-2 conductors may be used in wet or dry locations at temperatures not to exceed 90°C. Used for power and lighting indoors, exposed or concealed, in cable tray where identified for such use; in a raceway, or in dry locations and embedded in plaster or against other masonry. Voltage rating for XHHW-2 conductors is 600V.Construction
Compact stranded AA-8000 series aluminum conductor material per ASTM B800, ASTM B801, ASTM B836, ASTM B901 (Single Input Wire), as applicable. XLPE insulated XHHW-2 conductors are twisted with a bare conductor. A binder tape is wrapped over the conductors with interlocked aluminum tape applied over the assembly. Rated 90°C wet or dry and is flame and sunlight resistant.Specifications
Type MC cable with Type XHHW-2 conductors are manufactured and tested in accordance with the latest revisions of:- UL 44 for Thermoset-Insulated Wires and Cables
- UL 83 for Thermoplastic-Insulated Wires and Cables
- UL 1479 Standard for Fire Tests of Through-Penetration Firestops.
- UL Classified 1, 2, and 3 Hour Through-Penetration Firestop Systems.
- UL 1569 for Metal-Clad Cables.
- IEEE 1202 - Flame Testing of Cables for Use in Cable Tray, in Industrial and Commercial Occupancies (70,000 BTU/hr).
- ICEA T-29-520 - Vertical Cable Tray Flame Tests (210,000 Btu/hr).
- ICEA S-66-524 and requirements of the National Electric Code
- ICEA S-95-658 (NEMA WC 70) construction requirements
- Federal Specification J-C-30B
Color Code
Three Phase Conductors (3): Black, red, white
Ground Conductor (1): Bare
Other colors and stripes available by special order.
For Special Order- The entire assembly can be covered with a PVC or CPE outer jacket (black or color). Jacketed MC Cable may be used in wet locations, either direct burial, in underground conduit, or overhead.
- Halogen free jackets are available upon request
- A black jacket (on individual conductors) with color stripes can be requested.
- Bare Ground conductor available upon request.
- For sizes not listed above please contact sales.
Ampacity
To determine correct ampacity by conductor size, please consult the National Electric Code, latest edition. -
Type MC Four Conductor w/Ground Aluminum Armor XHHW-2 600V
Applications
Type MC Cable is primarily used for services, feeders, and branch circuits as specified in the 2011 National Electric Code. Type MC cable with Type XHHW-2 conductors may be used in wet or dry locations at temperatures not to exceed 90°C. Used for power and lighting indoors, exposed or concealed, in cable tray where identified for such use; in a raceway, or in dry locations and embedded in plaster or against other masonry. Voltage rating for XHHW-2 conductors is 600V.Construction
Compact stranded AA-8000 series aluminum conductor material per ASTM B800, ASTM B801, ASTM B836, ASTM B901 (Single Input Wire), as applicable. XLPE insulated XHHW-2 conductors are twisted with a bare conductor. A binder tape is wrapped over the conductors with interlocked aluminum tape applied over the assembly. Rated 90°C wet or dry and is flame and sunlight resistant.Specifications
Type MC cable with Type XHHW-2 conductors are manufactured and tested in accordance with the latest revisions of:- UL 44 for Thermoset-Insulated Wires and Cables
- UL 83 for Thermoplastic-Insulated Wires and Cables
- UL 1479 Standard for Fire Tests of Through-Penetration Firestops.
- UL Classified 1, 2, and 3 Hour Through-Penetration Firestop Systems.
- UL 1569 for Metal-Clad Cables.
- IEEE 1202 - Flame Testing of Cables for Use in Cable Tray, in Industrial and Commercial Occupancies (70,000 BTU/hr).
- ICEA T-29-520 - Vertical Cable Tray Flame Tests (210,000 Btu/hr).
- ICEA S-66-524 and requirements of the National Electric Code
- ICEA S-95-658 (NEMA WC 70) construction requirements
- Federal Specification J-C-30B
Color Code
Four Phase Conductors (4): Black, red, blue, white
Grounding Conductor (1): BareOther colors and stripes available by special order.
For Special Order- The entire assembly can be covered with a PVC or CPE outer jacket (black or color). Jacketed MC Cable may be used in wet locations, either direct burial, in underground conduit, or overhead.
- Halogen free jackets are available upon request
- A black jacket (on individual conductors) with color stripes can be requested.
- Bare Ground conductor available upon request.
- For sizes not listed above please contact sales.
Ampacity
To determine correct ampacity by conductor size, please consult the National Electric Code, latest edition. -
Three or Four Conductor UL Type MC, Aluminum Conductor, XHHW-2, AIA, 90°C Dry, Rated 600 V
Three or Four Conductor UL Type MC, Aluminum Conductor, XHHW-2, AIA, 90°C Dry, Rated 600 V
APPLICATIONS
UL Type MC cables with XHHW-2 conductors are primarily used for services, feeders and branch circuits in commercial and residential applications in accordance with the NEC. Suitable applications include for indoor power and lighting circuits, exposed or concealed, cable tray, raceway (conduit) and embedded in plaster or in contact with masonry. The cable is suitable for dry locations only at temperatures not to exceed 90°C. The cable is rated 600 V.CONSTRUCTION
Conductor: Annealed compact stranded AA-8000 series Aluminum Conductor Material (ACM).
Insulation: Abrasion, moisture, and heat resistant black crosslinked polyethylene (XLPE) with colored stripe.
Assembly: Cabled assembly with an equipment grounding conductor and a binder tape overall.
Armor: Aluminum Interlocked Armor (AIA).CONDUCTOR IDENTIFICATION
Three Conductors: Black, Black with Red Stripe, Black with White Stripe
Four Conductors: Black, Black with Red Stripe, Black with Blue Stripe, Black with White StripeVOLTAGE RATING: 600 V
TEMPERATURE RATING DRY 90 C MINIMUM BENDING RADIUS Not Under Tension: 7x outer diameter Under Tension (During Pull): 10.5x outer diameter
STANDARDS
These cables are manufactured and tested to meet or exceed the following standards:- ASTM B800 -- 8000 Series Aluminum Alloy Wire for Electrical Purposes - Annealed and Intermediate Tempers
- ASTM B801 -- Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy for Subsequent Covering or Insulation
- UL 44 -- Thermoset-Insulated Wires and Cables
- UL 1479 -- Fire Tests of Through-Penetration Firestops
- UL 1569 -- Metal-Clad Cables.
- ICEA S-95-658 / NEMA WC70 -- Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
- Federal Specification J-C-30B
LISTINGS AND CERTIFICATIONS
UL listed as Type MC -- File E487848
UL Classified 1, 2, and 3 Hour Through-Penetration Firestop Systems -
Three or Four Conductor UL Type MC, Aluminum Conductor THHN/THWN-2, AIA, 90°C Dry, Rated 600 V
Three or Four Conductor UL Type MC, Aluminum Conductor THHN/THWN-2, AIA, 90°C Dry, Rated 600 V
APPLICATIONS
UL Type MC cables with THHN/THWN-2 conductors are primarily used for services, feeders and branch circuits in commercial and residential applications in accordance with the NEC. Suitable applications include for indoor power and lighting circuits, exposed or concealed, cable tray, raceway (conduit) and embedded in plaster or in contact with masonry. The cable is suitable for dry locations only at temperatures not to exceed 90°C. The cable is rated 600 V.CONSTRUCTION
Conductor: Annealed compact stranded AA-8000 series Aluminum Conductor Material (ACM).
Insulation: Low coefficient of friction, abrasion, moisture, and heat resistant colored polyvinyl chloride (PVC).
Covering: Low coefficient of friction, abrasion, moisture, and heat resistant translucent Nylon polyamide.
Assembly: Cabled assembly with an equipment grounding conductor and a binder tape overall.
Armor: Aluminum Interlocked Armor (AIA).CONDUCTOR IDENTIFICATION
Three Conductors: Black, Black with Red Stripe, Black with White Stripe
Four Conductors: Black, Black with Red Stripe, Black with Blue Stripe, Black with White StripeVOLTAGE RATING: 600 V
TEMPERATURE RATING DRY 90 C MINIMUM BENDING RADIUS Not Under Tension: 7x outer diameter Under Tension (During Pull): 10.5x outer diameter
STANDARDS
These cables are manufactured and tested to meet or exceed the following standards:- ASTM B800 -- 8000 Series Aluminum Alloy Wire for Electrical Purposes - Annealed and Intermediate Tempers
- ASTM B801 -- Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy for Subsequent Covering or Insulation
- UL 83 -- Thermoplastic-Insulated Wires and Cables
- UL 1479 -- Fire Tests of Through-Penetration Firestops
- UL 1569 -- Metal-Clad Cables.
- ICEA S-95-658 / NEMA WC70 -- Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
- Federal Specification J-C-30B
LISTINGS AND CERTIFICATIONS
UL listed as Type MC -- File E487848
UL Classified 1, 2, and 3 Hour Through-Penetration Firestop Systems