Three or Four Conductor UL Type MC, Aluminum Conductor THHN/THWN-2, AIA, 90°C Dry, Rated 600 V


APPLICATIONS

UL Type MC cables with THHN/THWN-2 conductors are primarily used for services, feeders and branch circuits in commercial and residential applications in accordance with the NEC. Suitable applications include for indoor power and lighting circuits, exposed or concealed, cable tray, raceway (conduit) and embedded in plaster or in contact with masonry. The cable is suitable for dry locations only at temperatures not to exceed 90°C. The cable is rated 600 V.

CONSTRUCTION
Conductor: Annealed compact stranded AA-8000 series Aluminum Conductor Material (ACM).
Insulation: Low coefficient of friction, abrasion, moisture, and heat resistant colored polyvinyl chloride (PVC).
Covering: Low coefficient of friction, abrasion, moisture, and heat resistant translucent Nylon polyamide.
Assembly: Cabled assembly with an equipment grounding conductor and a binder tape overall.
Armor: Aluminum Interlocked Armor (AIA). 

CONDUCTOR IDENTIFICATION
Three Conductors: Black, Black with Red Stripe, Black with White Stripe
Four Conductors: Black, Black with Red Stripe, Black with Blue Stripe, Black with White Stripe

VOLTAGE RATING: 600 V


TEMPERATURE RATING
DRY 90 C



MINIMUM BENDING RADIUS
Not Under Tension: 7x outer diameter
Under Tension (During Pull):  10.5x outer diameter


STANDARDS
These cables are manufactured and tested to meet or exceed the following standards:

  • ASTM B800 -- 8000 Series Aluminum Alloy Wire for Electrical Purposes - Annealed and Intermediate Tempers
  • ASTM B801 -- Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy for Subsequent Covering or Insulation
  • UL 83 -- Thermoplastic-Insulated Wires and Cables
  • UL 1479 -- Fire Tests of Through-Penetration Firestops
  • UL 1569 -- Metal-Clad Cables.
  • ICEA S-95-658 / NEMA WC70 -- Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • Federal Specification J-C-30B

LISTINGS AND CERTIFICATIONS
UL listed as Type MC -- File E487848
UL Classified 1, 2, and 3 Hour Through-Penetration Firestop Systems



NOTES
Dimensions and weights are subject to standard manufacturing tolerances and are subject to change without notice.

1 - 38 of 38 | Results Per Page | View | Unit of Measure
1 

Item #

Cable
Description

Conductor
Size
(AWG or kcmil)

Conductors

Ground
Size
(AWG or kcmil)

Cabled Core
Diameter
(in)

Overall
Diameter
(in)

Aluminum
Weight
(lb/1000 ft)

Net
Weight
(lb/1000 ft)

N/A 4-4-4+6 N/A 4 N/A 3 N/A 6 N/A 0.66 N/A 0.957 N/A 312 N/A 364
N/A 3-3-3+6 N/A 3 N/A 3 N/A 6 N/A 0.71 N/A 1.011 N/A 353 N/A 411
N/A 2-2-2+6 N/A 2 N/A 3 N/A 6 N/A 0.78 N/A 1.076 N/A 404 N/A 468
N/A 2-2-2+4 N/A 2 N/A 3 N/A 4 N/A 0.78 N/A 1.076 N/A 419 N/A 483
N/A 1-1-1+4 N/A 1 N/A 3 N/A 4 N/A 0.89 N/A 1.19 N/A 490 N/A 580
N/A 1/0-1/0-1/0+4 N/A 1/0 N/A 3 N/A 4 N/A 0.97 N/A 1.27 N/A 567 N/A 667
N/A 2/0-2/0-2/0+4 N/A 2/0 N/A 3 N/A 4 N/A 1.06 N/A 1.356 N/A 663 N/A 772
N/A 3/0-3/0-3/0+4 N/A 3/0 N/A 3 N/A 4 N/A 1.16 N/A 1.457 N/A 779 N/A 900
N/A 4/0-4/0-4/0+2 N/A 4/0 N/A 3 N/A 2 N/A 1.27 N/A 1.569 N/A 952 N/A 1086
N/A 250-250-250+2 N/A 250 N/A 3 N/A 2 N/A 1.41 N/A 1.713 N/A 1088 N/A 1265
N/A 250-250-250+3/0 N/A 250 N/A 3 N/A 3/0 N/A 1.41 N/A 1.713 N/A 1186 N/A 1363
N/A 300-300-300+1 N/A 300 N/A 3 N/A 1 N/A 1.52 N/A 1.821 N/A 1269 N/A 1460
N/A 350-350-350+1 N/A 350 N/A 3 N/A 1 N/A 1.62 N/A 1.92 N/A 1431 N/A 1636
N/A 400-400-400+1 N/A 400 N/A 3 N/A 1 N/A 1.71 N/A 2.013 N/A 1591 N/A 1810
N/A 500-500-500+1 N/A 500 N/A 3 N/A 1 N/A 1.88 N/A 2.179 N/A 1907 N/A 2148
N/A 500-500-500+2/0 N/A 500 N/A 3 N/A 2/0 N/A 1.88 N/A 2.179 N/A 1954 N/A 2196
N/A 500-500-500+3/0 N/A 500 N/A 3 N/A 3/0 N/A 1.88 N/A 2.179 N/A 1988 N/A 2229
N/A 600-600-600+1 N/A 600 N/A 3 N/A 1 N/A 2.09 N/A 2.392 N/A 2236 N/A 2548
N/A 600-600-600+1/0 N/A 600 N/A 3 N/A 1/0 N/A 2.09 N/A 2.392 N/A 2257 N/A 2569
N/A 750-750-750+1/0 N/A 750 N/A 3 N/A 1/0 N/A 2.3 N/A 2.597 N/A 2723 N/A 3068
N/A 750-750-750+3/0 N/A 750 N/A 3 N/A 3/0 N/A 2.3 N/A 2.597 N/A 2783 N/A 3128
N/A 6-6-6-6+6 N/A 6 N/A 4 N/A 6 N/A 0.58 N/A 0.877 N/A 277 N/A 319
N/A 4-4-4-4+6 N/A 4 N/A 4 N/A 6 N/A 0.74 N/A 1.036 N/A 366 N/A 436
N/A 3-3-3-3+6 N/A 3 N/A 4 N/A 6 N/A 0.8 N/A 1.097 N/A 419 N/A 496
N/A 2-2-2-2+4 N/A 2 N/A 4 N/A 4 N/A 0.87 N/A 1.169 N/A 500 N/A 585
N/A 1-1-1-1+4 N/A 1 N/A 4 N/A 4 N/A 1 N/A 1.297 N/A 590 N/A 709
N/A 1/0-1/0-1/0-1/0+4 N/A 1/0 N/A 4 N/A 4 N/A 1.09 N/A 1.386 N/A 690 N/A 822
N/A 2/0-2/0-2/0-2/0+4 N/A 2/0 N/A 4 N/A 4 N/A 1.18 N/A 1.483 N/A 813 N/A 959
N/A 3/0-3/0-3/0-3/0+4 N/A 3/0 N/A 4 N/A 4 N/A 1.3 N/A 1.596 N/A 965 N/A 1126
N/A 4/0-4/0-4/0-4/0+2 N/A 4/0 N/A 4 N/A 2 N/A 1.42 N/A 1.722 N/A 1183 N/A 1361
N/A 250-250-250-250+1 N/A 250 N/A 4 N/A 1 N/A 1.584 N/A 1.884 N/A 1376 N/A 1612
N/A 300-300-300-300+1 N/A 300 N/A 4 N/A 1 N/A 1.704 N/A 2.004 N/A 1590 N/A 1846
N/A 350-350-350-350+1/0 N/A 350 N/A 4 N/A 1/0 N/A 1.815 N/A 2.115 N/A 1823 N/A 2097
N/A 400-400-400-400+1/0 N/A 400 N/A 4 N/A 1/0 N/A 1.919 N/A 2.219 N/A 2034 N/A 2325
N/A 500-500-500-500+3/0 N/A 500 N/A 4 N/A 3/0 N/A 2.105 N/A 2.405 N/A 2507 N/A 2830
N/A 600-600-600-600+3/0 N/A 600 N/A 4 N/A 3/0 N/A 2.344 N/A 2.644 N/A 2939 N/A 3354
N/A 750-750-750-750+3/0 N/A 750 N/A 4 N/A 3/0 N/A 2.574 N/A 2.874 N/A 3552 N/A 4012
N/A 750-750-750-750+750 N/A 750 N/A 4 N/A 750 N/A 2.574 N/A 2.874 N/A 4111 N/A 4571
1 - 38 of 38 | Results Per Page | View | Unit of Measure
1