PowerGuard AL 35kV 100% TR-XLPE CN XLPE UL Type MV-105 Electrical Properties (FLAT SPACED @ 7.5 INCHES)
PowerGuard AL 35kV 100% TR-XLPE CN XLPE UL Type MV-105 Electrical Properties
PowerGuard® AL 35kV 100% TR-XLPE CN XLPE UL Type MV-105 Electrical Properties (FLAT SPACED @ 7.5 INCHES)
NOTES
Conductor ampacities are based on the following:
• Load factor of 100% or 75%
• Earth thermal resistivity of 0.900ºC-m/W
• Ambient earth temperature of 20ºC
• Maximum conductor operating temperature of 105ºC
• Concentric neutral wires grounded at both ends (shield circulating currents flowing)
• Minimum separation of 3 m or 9.8 ft from any other underground electrical system or heat source
• Maximum load variation between phases of 10%
• Maximum 910 mm or 36 in depth of burial
• Cable arrangements:
○ Trefoil and touching
○ Flat and touching
○ Flat and spaced 190 mm or 7.5 in, center-to-center
• The ampacity values calculated may be limited by the maximum earth interface temperature due to soil moisture migration or dry out, and has not been considered here.
Updated 3/16/2022
Updated 3/16/2022
Unit of Measure
Items |
![]() A1/0-01UD35GT101X |
![]() A1/0-01UD35GT203X |
![]() A1/0-01UD35GT102X |
![]() A1/0-01UD35GT103X |
![]() A2/0-01UD35GT101X |
|||||
Conductor Size AWG or kcmil |
N/A 1/0 | N/A 1/0 | N/A 1/0 | N/A 1/0 | N/A 2/0 | |||||
Neutral Wires |
N/A 12 | N/A 13 | N/A 10 | N/A 7 | N/A 15 | |||||
Neutral Size AWG |
N/A 14 | N/A 16 | N/A 16 | N/A 16 | N/A 14 | |||||
Neutral Size |
N/A Full | N/A 2/3 | N/A 1/2 | N/A 1/3 | N/A Full | |||||
Sequence Impedance Pos/Neg (µO/feet) |
N/A 249.31 + j57.34 | N/A 248.6 + j58.15 | N/A 248.16 + j58.22 | N/A 247.72 + j58.27 | N/A 193.89 + j55.69 | |||||
Seq Impedance Zero (µO/feet) |
N/A 473.3 + j116.99 | N/A 538.21 + j188.58 | N/A 574.08 + j257.24 | N/A 597.79 + j368.65 | N/A 383.53 + j89.97 | |||||
Ampacity LF=100% (A) |
N/A 204 | N/A 204 | N/A 204 | N/A 204 | N/A 235 | |||||
Ampacity LF=75% (A) |
N/A 233 | N/A 233 | N/A 233 | N/A 233 | N/A 270 | |||||
|