Bare Aluminum AAC
Bare Aluminum AAC
Applications
Stranded 1350 aluminum conductors shown in this section of data are classified as follows:
Class AA For bare conductors usually used in overhead lines.
Class A For conductors to be covered with weather-resistant materials and for bare conductors where greater flexibility is required.
Compact strand conductor for use in bare overhead applications or for use with weather-resistant coverings or insulations is also available.
Classes refer to stranding and are an indication of relative conductor flexibility, AA being the least flexible, C the most flexible.
Construction
Aluminum alloy 1350-H19 wires, concentrically stranded.
Specifications
AAC bare conductors meet or exceed the following ASTM specifications :
B-230 Aluminum Wire, 1350-H19 for Electrical Purposes
B-231 Aluminum Conductors, Concentric-Lay-Stranded
B-400Compact Round Concentric-Lay-Stranded Aluminum 1350 Conductors
Notes
Stranded 1350 aluminum conductors shown in this section of data are classified as follows:
Class AA For bare conductors usually used in overhead lines.
Class A For conductors to be covered with weather-resistant materials and for bare conductors where greater flexibility is required.
Compact strand conductor for use in bare overhead applications or for use with weather-resistant coverings or insulations is also available.
Classes refer to stranding and are an indication of relative conductor flexibility, AA being the least flexible, C the most flexible.
Construction
Aluminum alloy 1350-H19 wires, concentrically stranded.
Specifications
AAC bare conductors meet or exceed the following ASTM specifications :
B-230 Aluminum Wire, 1350-H19 for Electrical Purposes
B-231 Aluminum Conductors, Concentric-Lay-Stranded
B-400
Notes
- Resistance is calculated using ASTM standard increments of stranding and metal conductivity of 52.5% IACS, AC resistance at 60Hz
- Current ratings are based on 75 ºC conductor temperature, 25 ºC ambient, 2ft/s wind, 96/watts/sq.ft sun, .05 coefficients of emissivity and absorption.
Unit of Measure
Items |
/Asset/Bare-Aluminum-Wire.jpg Peachbell Bare Aluminum AAC |
/Asset/Bare-Aluminum-Wire.jpg Rose Bare Aluminum AAC |
/Asset/Bare-Aluminum-Wire.jpg Iris Bare Aluminum AAC |
/Asset/Bare-Aluminum-Wire.jpg Pansy Bare Aluminum AAC |
/Asset/Bare-Aluminum-Wire.jpg Poppy Bare Aluminum AAC |
|||||
Size (AWG or kcmil) |
N/A 6 | N/A 4 | N/A 2 | N/A 1 | N/A 1/0 | |||||
No. of Wires | N/A 7 | |||||||||
CLASS | N/A A | N/A A | N/A A AA | N/A A AA | N/A A AA | |||||
Diameter Individual Wire |
N/A 0.0612 Inches | N/A 0.0772 Inches | N/A 0.0974 Inches | N/A 0.1093 Inches | N/A 0.1228 Inches | |||||
Diameter Complete Cable (O.D.) |
N/A 0.184 Inches | N/A 0.232 Inches | N/A 0.292 Inches | N/A 0.328 Inches | N/A 0.368 Inches | |||||
Cross Sectional Area |
N/A 0.0206 sq.inches | N/A 0.0328 sq.inches | N/A 0.0521 sq.inches | N/A 0.0657 sq.inches | N/A 0.0829 sq.inches | |||||
Weight (lb/1000 ft) |
N/A 24.6 Lbs | N/A 39.2 Lbs | N/A 62.3 Lbs | N/A 99.1 Lbs | N/A 78.5 Lbs | |||||
Rated Breaking Strength |
N/A 563 Lbs | N/A 881 Lbs | N/A 1350 Lbs | N/A 1640 Lbs | N/A 1990 Lbs | |||||
Resistance DC 20 ºC Per MFT (ohm) |
N/A 0.658 Ω | N/A 0.414 Ω | N/A 0.260 Ω | N/A 0.207 Ω | N/A 0.164 Ω | |||||
Resistance AC 75 ºC per MFT (ohm) |
N/A 0.805 Ω | N/A 0.506 Ω | N/A 0.318 Ω | N/A 0.252 Ω | N/A 0.202 Ω | |||||
Rating | N/A 103 Amps | N/A 138 Amps | N/A 185 Amps | N/A 214 Amps | N/A 247 Amps | |||||
|