PowerGuard® AL 35kV 100% TR-XLPE CN XLPE UL Type MV-105 Electrical Properties (FLAT SPACED @ 7.5 INCHES)
NOTES
Conductor ampacities are based on the following:
• Load factor of 100% or 75%
• Earth thermal resistivity of 0.900ºC-m/W
• Ambient earth temperature of 20ºC
• Maximum conductor operating temperature of 105ºC
• Concentric neutral wires grounded at both ends (shield circulating currents flowing)
• Minimum separation of 3 m or 9.8 ft from any other underground electrical system or heat source
• Maximum load variation between phases of 10%
• Maximum 910 mm or 36 in depth of burial
• Cable arrangements:
○ Trefoil and touching
○ Flat and touching
○ Flat and spaced 190 mm or 7.5 in, center-to-center
• The ampacity values calculated may be limited by the maximum earth interface temperature due to soil moisture migration or dry out, and has not been considered here.
Updated 3/16/2022
Updated 3/16/2022
Unit of Measure
Conductor
|
N/A 250 |
Neutral
|
N/A 8 |
Neutral
|
N/A 16 |
Neutral
|
N/A 1/6 |
Sequence
|
N/A 99.82 + j50.9 |
Seq
|
N/A 442.48 + j327.16 |
Ampacity
|
N/A 339 |
Ampacity
|
N/A 392 |