Aluminum HYLUG™ Terminal and HYLINK™ Splice Connectors
®             
® LISTED WIRE CONNECTOR


TYPES YA-A and YS-A
90°C, up to 35 kV

RECOMMENDED FOR USE ON COPPER AND ALUMINUM CONDUCTOR

INSTALLATION INSTRUCTIONS:

1             Use a HYLUG™ terminal or HYLINK™ splice
marked for the wire size to be used. 

Never use a copper crimp connector on aluminum wire.    
2 Strip the wire insulation without nicking
or ringing the conductor strands
3  Always wire brush the stripped portion
of the conductor to remove oxide film.
4  Insert the conductor all the way into the barrel and crimp the
connector using a
die index number and color marked
on the connector. Be sure orientation is correct before crimping.
5  Wire brush any unplated surface to which the HYLUG™
will be attached and coat the contact surface
with PENETROX™ joint compound

 Remove any excess PENETROX™ before taping.


Dieless tools and nest/indenter tools will have a completed crimp similar to illustration shown BELOW:

Other die sets listed have a completed crimp of a more circumferential nature and will look similar to this illustration: