PowerGuard® AL 35kV 100% TR-XLPE CN XLPE UL Type MV-105 Electrical Properties  (FLAT SPACED @ 7.5 INCHES)


NOTES

Conductor ampacities are based on the following:

• Load factor of 100% or 75%
• Earth thermal resistivity of 0.900ºC-m/W
• Ambient earth temperature of 20ºC
• Maximum conductor operating temperature of 105ºC
• Concentric neutral wires grounded at both ends (shield circulating currents flowing)
• Minimum separation of 3 m or 9.8 ft from any other underground electrical system or heat source
• Maximum load variation between phases of 10%
• Maximum 910 mm or 36 in depth of burial
• Cable arrangements:
○ Trefoil and touching
○ Flat and touching
○ Flat and spaced 190 mm or 7.5 in, center-to-center
• The ampacity values calculated may be limited by the maximum earth interface temperature due to soil moisture migration or dry out, and has not been considered here.


Updated 3/16/2022
AWG MV AL XLPE CU CN
Unit of Measure
Items AWG MV AL XLPE CU CN
A1/0-01UD35GT101X
AWG MV AL XLPE CU CN
A1/0-01UD35GT203X
AWG MV AL XLPE CU CN
A1/0-01UD35GT102X
AWG MV AL XLPE CU CN
A1/0-01UD35GT103X
AWG MV AL XLPE CU CN
A2/0-01UD35GT101X
Conductor
Size
AWG
or
kcmil
N/A 1/0 N/A 1/0 N/A 1/0 N/A 1/0 N/A 2/0
Neutral
Wires
N/A 12 N/A 13 N/A 10 N/A 7 N/A 15
Neutral
Size
AWG
N/A 14 N/A 16 N/A 16 N/A 16 N/A 14
Neutral
Size
N/A Full N/A 2/3 N/A 1/2 N/A 1/3 N/A Full
Sequence
Impedance
Pos/Neg
(µO/feet)
N/A 249.31 + j57.34 N/A 248.6 + j58.15 N/A 248.16 + j58.22 N/A 247.72 + j58.27 N/A 193.89 + j55.69
Seq
Impedance
Zero
(µO/feet)
N/A 473.3 + j116.99 N/A 538.21 + j188.58 N/A 574.08 + j257.24 N/A 597.79 + j368.65 N/A 383.53 + j89.97
Ampacity
LF=100%
(A)
N/A 204 N/A 204 N/A 204 N/A 204 N/A 235
Ampacity
LF=75%
(A)
N/A 233 N/A 233 N/A 233 N/A 233 N/A 270