Application
Used to supply power, usually from a pole-mounted transformer, to the user's service head where connection to the service entrance cable is made. Also suitable for installations for street lighting, security lights, and temporary service for construction. To be used at voltages of 600 volts phase-to-phase or less and at conductor temperatures not to exceed 75 ºC for polyethylene insulated conductors and 90 ºC for crosslinked polyethylene (XLP) insulated conductors.

Specifications
Meets or exceeds the following ASTM specifications:
  • B-1 Hard-Drawn Copper Wire.
  • B-3 Soft or Annealed Copper Wire.
  • B-8 Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard, or Soft.
Meets or exceeds all applicable requirements of ANSI/ICEA S-76-474 for polyethylene and crosslinked polyethylene insulated conductors.

Construction
Conductors are concentrically stranded compressed soft copper insulated with either crosslinked polyethylene, or conventional polyethylene.
Neutral messengers are either solid or concentrically stranded bare hard-drawn copper.

Notes:
  • Code words for XLP insulated products are formed by adding ""XLP"" to the conventional polyethylene code words above (e.g.- Atlanta/XLP).
  • Ampacity figures for black insulation only. Based on conductor temperature of 75 ºC for polyethylene insulated conductors, 90 ºC for XLP insulated conductors, ambient temperature of 40 ºC 2 ft./sec. wind in sun.
Quadruplex Service Drop Cable<br>Copper Conductor
Items Quadruplex Service Drop Cable<br>Copper Conductor
Atlanta
Copper Quadruplex Service Drop Cable
Quadruplex Service Drop Cable<br>Copper Conductor
Tallahassee
Copper Quadruplex Service Drop Cable
Quadruplex Service Drop Cable<br>Copper Conductor
Richmond
Copper Quadruplex Service Drop Cable
Quadruplex Service Drop Cable<br>Copper Conductor
BatonRouge
Copper Quadruplex Service Drop Cable
Quadruplex Service Drop Cable<br>Copper Conductor
Jackson
Copper Quadruplex Service Drop Cable
Phase
Conductor
Size
AWG
N/A 6 N/A 6 N/A 4 N/A 4 N/A 2
Phase
Conductor
Stranding
N/A 7
Phase
Conductor
Cover
Thickness
(mils)
N/A 45
Neutral
Messenger
Size
AWG
N/A 6 N/A 6 N/A 4 N/A 4 N/A 2
Neutral
Messenger
Stranding
N/A 1 N/A 7 N/A 1 N/A 7 N/A 1
Neutral
Messenger
Rated
Strength
(lbs.)
N/A 1280 N/A 1228 N/A 1970 N/A 1938 N/A 3003
Nominal
Lay
Length
(inches)
N/A 20.58 N/A 20.58 N/A 20.58 N/A 20.58 N/A 25.42
Weight
(lb/1000 ft)
XLP
N/A 359 N/A 361 N/A 560 N/A 563 N/A 879
Weight
(lb/1000 ft)
Poly
N/A 344 N/A 346 N/A 542 N/A 545 N/A 856
Allowable
Ampacities
XLP
N/A 95 N/A 95 N/A 125 N/A 125 N/A 170
Allowable
Ampacities
Poly
N/A 75 N/A 75 N/A 100 N/A 100 N/A 135