Copper Quadruplex Service Drop Cable
Quadruplex Service Drop Cable
Copper Conductor
Copper Conductor
Application
Used to supply power, usually from a pole-mounted transformer, to the user's service head where connection to the service entrance cable is made. Also suitable for installations for street lighting, security lights, and temporary service for construction. To be used at voltages of 600 volts phase-to-phase or less and at conductor temperatures not to exceed 75 ºC for polyethylene insulated conductors and 90 ºC for crosslinked polyethylene (XLP) insulated conductors.
Specifications
Meets or exceeds the following ASTM specifications:
Construction
Conductors are concentrically stranded compressed soft copper insulated with either crosslinked polyethylene, or conventional polyethylene.
Neutral messengers are either solid or concentrically stranded bare hard-drawn copper.
Notes:
Used to supply power, usually from a pole-mounted transformer, to the user's service head where connection to the service entrance cable is made. Also suitable for installations for street lighting, security lights, and temporary service for construction. To be used at voltages of 600 volts phase-to-phase or less and at conductor temperatures not to exceed 75 ºC for polyethylene insulated conductors and 90 ºC for crosslinked polyethylene (XLP) insulated conductors.
Specifications
Meets or exceeds the following ASTM specifications:
- B-1 Hard-Drawn Copper Wire.
- B-3 Soft or Annealed Copper Wire.
- B-8 Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard, or Soft.
Construction
Conductors are concentrically stranded compressed soft copper insulated with either crosslinked polyethylene, or conventional polyethylene.
Neutral messengers are either solid or concentrically stranded bare hard-drawn copper.
Notes:
- Code words for XLP insulated products are formed by adding ""XLP"" to the conventional polyethylene code words above (e.g.- Atlanta/XLP).
- Ampacity figures for black insulation only. Based on conductor temperature of 75 ºC for polyethylene insulated conductors, 90 ºC for XLP insulated conductors, ambient temperature of 40 ºC 2 ft./sec. wind in sun.
Item # |
Phase
|
Phase
|
Phase
|
Neutral
|
Neutral
|
Neutral
|
Nominal
|
Weight
|
Weight
|
Allowable
|
Allowable
|
---|---|---|---|---|---|---|---|---|---|---|---|
Atlanta Atlanta/Asset/CU-QUAD-SERVICE-DROP.jpg |
Phase Conductor Size AWG N/A 6 |
Phase Conductor Stranding N/A 7 |
Phase Conductor Cover Thickness (mils) N/A 45 |
Neutral Messenger Size AWG N/A 6 |
Neutral Messenger Stranding N/A 1 |
Neutral Messenger Rated Strength (lbs.) N/A 1280 |
Nominal Lay Length (inches) N/A 20.58 |
Weight (lb/1000 ft) XLP N/A 359 |
Weight (lb/1000 ft) Poly N/A 344 |
Allowable Ampacities XLP N/A 95 |
Allowable Ampacities Poly N/A 75 |
Tallahassee Tallahassee/Asset/CU-QUAD-SERVICE-DROP.jpg |
Phase Conductor Size AWG N/A 6 |
Phase Conductor Stranding N/A 7 |
Phase Conductor Cover Thickness (mils) N/A 45 |
Neutral Messenger Size AWG N/A 6 |
Neutral Messenger Stranding N/A 7 |
Neutral Messenger Rated Strength (lbs.) N/A 1228 |
Nominal Lay Length (inches) N/A 20.58 |
Weight (lb/1000 ft) XLP N/A 361 |
Weight (lb/1000 ft) Poly N/A 346 |
Allowable Ampacities XLP N/A 95 |
Allowable Ampacities Poly N/A 75 |
Richmond Richmond/Asset/CU-QUAD-SERVICE-DROP.jpg |
Phase Conductor Size AWG N/A 4 |
Phase Conductor Stranding N/A 7 |
Phase Conductor Cover Thickness (mils) N/A 45 |
Neutral Messenger Size AWG N/A 4 |
Neutral Messenger Stranding N/A 1 |
Neutral Messenger Rated Strength (lbs.) N/A 1970 |
Nominal Lay Length (inches) N/A 20.58 |
Weight (lb/1000 ft) XLP N/A 560 |
Weight (lb/1000 ft) Poly N/A 542 |
Allowable Ampacities XLP N/A 125 |
Allowable Ampacities Poly N/A 100 |
BatonRouge BatonRouge/Asset/CU-QUAD-SERVICE-DROP.jpg |
Phase Conductor Size AWG N/A 4 |
Phase Conductor Stranding N/A 7 |
Phase Conductor Cover Thickness (mils) N/A 45 |
Neutral Messenger Size AWG N/A 4 |
Neutral Messenger Stranding N/A 7 |
Neutral Messenger Rated Strength (lbs.) N/A 1938 |
Nominal Lay Length (inches) N/A 20.58 |
Weight (lb/1000 ft) XLP N/A 563 |
Weight (lb/1000 ft) Poly N/A 545 |
Allowable Ampacities XLP N/A 125 |
Allowable Ampacities Poly N/A 100 |
Jackson Jackson/Asset/CU-QUAD-SERVICE-DROP.jpg |
Phase Conductor Size AWG N/A 2 |
Phase Conductor Stranding N/A 7 |
Phase Conductor Cover Thickness (mils) N/A 45 |
Neutral Messenger Size AWG N/A 2 |
Neutral Messenger Stranding N/A 1 |
Neutral Messenger Rated Strength (lbs.) N/A 3003 |
Nominal Lay Length (inches) N/A 25.42 |
Weight (lb/1000 ft) XLP N/A 879 |
Weight (lb/1000 ft) Poly N/A 856 |
Allowable Ampacities XLP N/A 170 |
Allowable Ampacities Poly N/A 135 |
Seattle Seattle/Asset/CU-QUAD-SERVICE-DROP.jpg |
Phase Conductor Size AWG N/A 2 |
Phase Conductor Stranding N/A 7 |
Phase Conductor Cover Thickness (mils) N/A 45 |
Neutral Messenger Size AWG N/A 2 |
Neutral Messenger Stranding N/A 7 |
Neutral Messenger Rated Strength (lbs.) N/A 3050 |
Nominal Lay Length (inches) N/A 25.42 |
Weight (lb/1000 ft) XLP N/A 883 |
Weight (lb/1000 ft) Poly N/A 860 |
Allowable Ampacities XLP N/A 170 |
Allowable Ampacities Poly N/A 135 |
Nashville Nashville/Asset/CU-QUAD-SERVICE-DROP.jpg |
Phase Conductor Size AWG N/A 1/0 |
Phase Conductor Stranding N/A 19 |
Phase Conductor Cover Thickness (mils) N/A 60 |
Neutral Messenger Size AWG N/A 1/0 |
Neutral Messenger Stranding N/A 7 |
Neutral Messenger Rated Strength (lbs.) N/A 4752 |
Nominal Lay Length (inches) N/A 25.42 |
Weight (lb/1000 ft) XLP N/A 1405 |
Weight (lb/1000 ft) Poly N/A 1368 |
Allowable Ampacities XLP N/A 230 |
Allowable Ampacities Poly N/A 180 |
Lincoln Lincoln/Asset/CU-QUAD-SERVICE-DROP.jpg |
Phase Conductor Size AWG N/A 2/0 |
Phase Conductor Stranding N/A 19 |
Phase Conductor Cover Thickness (mils) N/A 60 |
Neutral Messenger Size AWG N/A 2/0 |
Neutral Messenger Stranding N/A 7 |
Neutral Messenger Rated Strength (lbs.) N/A 5926 |
Nominal Lay Length (inches) N/A 29.97 |
Weight (lb/1000 ft) XLP N/A 1761 |
Weight (lb/1000 ft) Poly N/A 1720 |
Allowable Ampacities XLP N/A 265 |
Allowable Ampacities Poly N/A 205 |
Raleigh Raleigh/Asset/CU-QUAD-SERVICE-DROP.jpg |
Phase Conductor Size AWG N/A 3/0 |
Phase Conductor Stranding N/A 19 |
Phase Conductor Cover Thickness (mils) N/A 60 |
Neutral Messenger Size AWG N/A 3/0 |
Neutral Messenger Stranding N/A 7 |
Neutral Messenger Rated Strength (lbs.) N/A 7366 |
Nominal Lay Length (inches) N/A 35.18 |
Weight (lb/1000 ft) XLP N/A 2209 |
Weight (lb/1000 ft) Poly N/A 2163 |
Allowable Ampacities XLP N/A 305 |
Allowable Ampacities Poly N/A 235 |
Denver Denver/Asset/CU-QUAD-SERVICE-DROP.jpg |
Phase Conductor Size AWG N/A 4/0 |
Phase Conductor Stranding N/A 19 |
Phase Conductor Cover Thickness (mils) N/A 60 |
Neutral Messenger Size AWG N/A 4/0 |
Neutral Messenger Stranding N/A 7 |
Neutral Messenger Rated Strength (lbs.) N/A 9154 |
Nominal Lay Length (inches) N/A 35.18 |
Weight (lb/1000 ft) XLP N/A 2773 |
Weight (lb/1000 ft) Poly N/A 2721 |
Allowable Ampacities XLP N/A 350 |
Allowable Ampacities Poly N/A 270 |