Print Back

PowerGuard® AL 35kV 100% TR-XLPE CN XLPE UL Type MV-105 Current Withstand

Unit of Measure

Specifications

Conductor
Size
(AWG
or
kcmil)

N/A 2/0

Neutral
Wires

N/A 12

Neutral
Size
(AWG)

N/A 16

Neutral
Size

N/A 1/2

Conductor
Resistance
@ 20º C
(O / 1000 ft)

N/A 0.75241

Capacitance
(µF / 1000 ft)

N/A 0.04572

Short-Circuit Current
-
Conductor

-
8 Cycles
-
(A)

N/A 16147

Short-Circuit Current
-
Shield Wires
-
8 Cycles
-
(A)

N/A 7329

Short-Circuit Current
-
Conductor

-
16 Cycles
-
(A)

N/A 11418

Short-Circuit Current
-
Shield Wires
-
16 Cycles
-
(A)

N/A 5182

Short-Circuit Current
-
Conductor

-
24 Cycles
-
(A)

N/A 9322

Short-Circuit Current
-
Shield Wires
-
24 Cycles
-
(A)

N/A 4231