Print Back
Applications
To supply power from the utility's lines to the consumer's weatherhead. For service at 600 volts or less (phase to phase) at a conductor temperature of 75 ºC maximum for polyethylene Insulation or 90 ºC maximum for crosslinked insulation.

Construction
Concentric strand or compressed 1350-H19 conductor, polyethylene or crosslinked polyethylene insulation, concentric strand 6201 alloy neutral messenger.

Standards
  • B-230 Aluminum Wire 1350-H19 for Electrical Purposes.
  • B-231 Aluminum Conductors, Concentric-Lay-Stranded.
  • B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR).
  • B-399 Concentric-Lay-Stranded 6201-T81 Aluminum Alloy Conductors.
  • B-498 Zinc-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR).
  • Triplex Service Drop cable meets or exceeds all applicable requirements of ANSI/ICEA body S-76-474
Unit of Measure

Specifications

Code Name

N/A Echinus

Phase
Conductor
Size/AWG

N/A 1/0

Phase
Conductor
Stranding

N/A 19

Phase
Conductor
Insulation
Thickness

N/A 60 mls

Bare
Neutral
Messenger
Size/AWG

N/A 2

Bare
Neutral
Messenger
Stranding

N/A 7

Bare
Neutral
Messenger
Breaking
Strength

N/A 2800 Lbs

Weight
Per
(lb/1000 ft)
XLP

N/A 358.8 Lbs

Weight
(lb/1000 ft)
Poly

N/A 343.1 Lbs

Ampacity
XLP

N/A 205 Amps

Ampacity
Poly

N/A 160 Amps