Bare Aluminum AAAC 6201 Alloy
Bare Aluminum AAAC 6201 Alloy
Applications
Used as bare overhead conductor for primary and secondary distribution. Designed utilizing a high-strength aluminum alloy to achieve a high strength-to-weight ratio; affords better sag characteristics. Aluminum alloy gives AAAC higher resistance to corrosion than ACSR.
Construction
Standard 6201-T81 high strength aluminum conductors, conforming to ASTM Specification B-399, are concentric-lay- stranded, similar in construction and appearance to 1350 grade aluminum conductors. Standard 6201 alloy conductors were developed to fill the need for an economical conductor for overhead applications requiring higher strength than that obtainable with 1350 grade aluminum conductors, but without a steel core. The DC resistance at 20 ºC of the 6201-T81 conductors and of the standard ACSRs of the same diameter are approximately the same. Conductors of the 6201-T81 alloys are harder and, therefore, have a greater resistance to abrasion than conductors of 1350-H19 grade aluminum.
Specifications
AAAC bare conductor meets or exceeds the following ASTM specifications :
B-398 Aluminum Alloy 6201-T81 Wire for Electrical Purposes
B-399 Concentric-Lay-Stranded 6201-T81 Aluminum Alloy Conductors.
Notes
Used as bare overhead conductor for primary and secondary distribution. Designed utilizing a high-strength aluminum alloy to achieve a high strength-to-weight ratio; affords better sag characteristics. Aluminum alloy gives AAAC higher resistance to corrosion than ACSR.
Construction
Standard 6201-T81 high strength aluminum conductors, conforming to ASTM Specification B-399, are concentric-lay- stranded, similar in construction and appearance to 1350 grade aluminum conductors. Standard 6201 alloy conductors were developed to fill the need for an economical conductor for overhead applications requiring higher strength than that obtainable with 1350 grade aluminum conductors, but without a steel core. The DC resistance at 20 ºC of the 6201-T81 conductors and of the standard ACSRs of the same diameter are approximately the same. Conductors of the 6201-T81 alloys are harder and, therefore, have a greater resistance to abrasion than conductors of 1350-H19 grade aluminum.
Specifications
AAAC bare conductor meets or exceeds the following ASTM specifications :
B-398 Aluminum Alloy 6201-T81 Wire for Electrical Purposes
B-399 Concentric-Lay-Stranded 6201-T81 Aluminum Alloy Conductors.
Notes
- Resistance is calculated using ASTM standard increments of stranding and metal conductivity of 52.5% IACS, AC resistance at 60Hz
- Current ratings are based on 75 ºC conductor temperature, 25 ºC ambient, 2ft/s wind, 96/watts/sq.ft sun, 0.5 coefficients of emissivity and absorption.
Item # |
Size
|
Strand |
Approximate
|
Stranding |
Diameter
|
Diameter
|
Cross
|
Weight
|
Rated
|
Rating |
---|---|---|---|---|---|---|---|---|---|---|
Akron Akron/Asset/Bare-Aluminum-Wire.jpg |
Size KCM N/A 30.58 |
Strand N/A 7/w |
Approximate EC Cond. w/Equivalent Resistance N/A 6 |
Stranding N/A 6/1 |
Diameter Individual Wire N/A 0.0661 Inches |
Diameter Complete Cable N/A .198 Inches |
Cross Sectional Area N/A 0.0240 sq.inches |
Weight (lb/1000 ft) N/A 28.7 Lbs |
Rated Breaking Strength N/A 1110 Lbs |
Rating N/A 107 Amps |
Alton Alton/Asset/Bare-Aluminum-Wire.jpg |
Size KCM N/A 48.69 |
Strand N/A 7/w |
Approximate EC Cond. w/Equivalent Resistance N/A 4 |
Stranding N/A 6/1 |
Diameter Individual Wire N/A 0.0834 Inches |
Diameter Complete Cable N/A .250 Inches |
Cross Sectional Area N/A 0.0382 sq.inches |
Weight (lb/1000 ft) N/A 45.7 Lbs |
Rated Breaking Strength N/A 1760 Lbs |
Rating N/A 143 Amps |
Ames Ames/Asset/Bare-Aluminum-Wire.jpg |
Size KCM N/A 77.47 |
Strand N/A 7/w |
Approximate EC Cond. w/Equivalent Resistance N/A 2 |
Stranding N/A 6/1 |
Diameter Individual Wire N/A 0.1052 Inches |
Diameter Complete Cable N/A .316 Inches |
Cross Sectional Area N/A 0.0608 sq.inches |
Weight (lb/1000 ft) N/A 72.7 Lbs |
Rated Breaking Strength N/A 2800 Lbs |
Rating N/A 191 Amps |
Azusa Azusa/Asset/Bare-Aluminum-Wire.jpg |
Size KCM N/A 123.3 |
Strand N/A 7/w |
Approximate EC Cond. w/Equivalent Resistance N/A 1/0 |
Stranding N/A 6/1 |
Diameter Individual Wire N/A 0.1327 Inches |
Diameter Complete Cable N/A .398 Inches |
Cross Sectional Area N/A 0.0968 sq.inches |
Weight (lb/1000 ft) N/A 115.7 Lbs |
Rated Breaking Strength N/A 4460 Lbs |
Rating N/A 256 Amps |
Anaheim Anaheim/Asset/Bare-Aluminum-Wire.jpg |
Size KCM N/A 155.4 |
Strand N/A 7/w |
Approximate EC Cond. w/Equivalent Resistance N/A 2/0 |
Stranding N/A 6/1 |
Diameter Individual Wire N/A 0.1490 Inches |
Diameter Complete Cable N/A .447 Inches |
Cross Sectional Area N/A 0.1221 sq.inches |
Weight (lb/1000 ft) N/A 145.9 Lbs |
Rated Breaking Strength N/A 5390 Lbs |
Rating N/A 296 Amps |
Amherst Amherst/Asset/Bare-Aluminum-Wire.jpg |
Size KCM N/A 195.7 |
Strand N/A 7/w |
Approximate EC Cond. w/Equivalent Resistance N/A 3/0 |
Stranding N/A 6/1 |
Diameter Individual Wire N/A 0.1672 Inches |
Diameter Complete Cable N/A .502 Inches |
Cross Sectional Area N/A 0.1537 sq.inches |
Weight (lb/1000 ft) N/A 183.7 Lbs |
Rated Breaking Strength N/A 6790 Lbs |
Rating N/A 342 Amps |
Alliance Alliance/Asset/Bare-Aluminum-Wire.jpg |
Size KCM N/A 246.9 |
Strand N/A 7/w |
Approximate EC Cond. w/Equivalent Resistance N/A 4/0 |
Stranding N/A 6/1 |
Diameter Individual Wire N/A 0.1878 Inches |
Diameter Complete Cable N/A .563 Inches |
Cross Sectional Area N/A 0.1939 sq.inches |
Weight (lb/1000 ft) N/A 231.8 Lbs |
Rated Breaking Strength N/A 8560 Lbs |
Rating N/A 395 Amps |
Butte Butte/Asset/Bare-Aluminum-Wire.jpg |
Size KCM N/A 312.8 |
Strand N/A 19/w |
Approximate EC Cond. w/Equivalent Resistance N/A 266.8 |
Stranding N/A 26/7 |
Diameter Individual Wire N/A 0.1283 Inches |
Diameter Complete Cable N/A .642 Inches |
Cross Sectional Area N/A 0.2456 sq.inches |
Weight (lb/1000 ft) N/A 293.6 Lbs |
Rated Breaking Strength N/A 11000 Lbs |
Rating N/A 460 Amps |
Canton Canton/Asset/Bare-Aluminum-Wire.jpg |
Size KCM N/A 394.5 |
Strand N/A 19/w |
Approximate EC Cond. w/Equivalent Resistance N/A 336.4 |
Stranding N/A 26/7 |
Diameter Individual Wire N/A 0.1441 Inches |
Diameter Complete Cable N/A .721 Inches |
Cross Sectional Area N/A 0.3098 sq.inches |
Weight (lb/1000 ft) N/A 370.3 Lbs |
Rated Breaking Strength N/A 13300 Lbs |
Rating N/A 532 Amps |
Cairo Cairo/Asset/Bare-Aluminum-Wire.jpg |
Size KCM N/A 465.4 |
Strand N/A 19/w |
Approximate EC Cond. w/Equivalent Resistance N/A 397.5 |
Stranding N/A 26/7 |
Diameter Individual Wire N/A 0.1565 Inches |
Diameter Complete Cable N/A .783 Inches |
Cross Sectional Area N/A 0.3655 sq.inches |
Weight (lb/1000 ft) N/A 436.9 Lbs |
Rated Breaking Strength N/A 15600 Lbs |
Rating N/A 590 Amps |
Darien Darien/Asset/Bare-Aluminum-Wire.jpg |
Size KCM N/A 559.5 |
Strand N/A 19/w |
Approximate EC Cond. w/Equivalent Resistance N/A 477.0 |
Stranding N/A 26/7 |
Diameter Individual Wire N/A 0.1716 Inches |
Diameter Complete Cable N/A .858 Inches |
Cross Sectional Area N/A 0.4394 sq.inches |
Weight (lb/1000 ft) N/A 525.2 Lbs |
Rated Breaking Strength N/A 18800 Lbs |
Rating N/A 663 Amps |
Elgin Elgin/Asset/Bare-Aluminum-Wire.jpg |
Size KCM N/A 652.4 |
Strand N/A 19/w |
Approximate EC Cond. w/Equivalent Resistance N/A 556.5 |
Stranding N/A 26/7 |
Diameter Individual Wire N/A 0.1853 Inches |
Diameter Complete Cable N/A .927 Inches |
Cross Sectional Area N/A 0.5124 sq.inches |
Weight (lb/1000 ft) N/A 612.4 Lbs |
Rated Breaking Strength N/A 21900 Lbs |
Rating N/A 729 Amps |
Flint Flint/Asset/Bare-Aluminum-Wire.jpg |
Size KCM N/A 740.8 |
Strand N/A 37/w |
Approximate EC Cond. w/Equivalent Resistance N/A 636.0 |
Stranding N/A 26/7 |
Diameter Individual Wire N/A 0.1415 Inches |
Diameter Complete Cable N/A .991 Inches |
Cross Sectional Area N/A 0.5818 sq.inches |
Weight (lb/1000 ft) N/A 695.5 Lbs |
Rated Breaking Strength N/A 24400 Lbs |
Rating N/A 790 Amps |
Greeley Greeley/Asset/Bare-Aluminum-Wire.jpg |
Size KCM N/A 927.2 |
Strand N/A 37/w |
Approximate EC Cond. w/Equivalent Resistance N/A 795.0 |
Stranding N/A 26/7 |
Diameter Individual Wire N/A 0.1583 Inches |
Diameter Complete Cable N/A 1.108 Inches |
Cross Sectional Area N/A 0.7282 sq.inches |
Weight (lb/1000 ft) N/A 870.4 Lbs |
Rated Breaking Strength N/A 30500 Lbs |
Rating N/A 908 Amps |